Xtreme Power Conversion Corporation
P90L 6kVA & 10kVA User’s Manual
Page 25
Uninterruptible Power Supply
5) Calibration
Interface
Description
The Batt, Inv, and Chg calibrations can be adjusted to ensure the front
panel display value matches the actual voltages measured in the UPS
with a multimeter.
1. Batt:
Calibrate the battery voltage measurement; the calibration
range is from 0V to 5.7V, the default value is 0V. It is available on all
operation modes.
2.
Inv:
Adjust the inverter output voltage; the adjustable range is from
0V to 6.4V, the default value is 0V. It is only available in line / battery
/ converter mode;
3.
Chg:
Adjust the Charger output voltage; the adjustable value is from
0V to 6.9V, the default value is 0V. It is only available in bypass / line
/ ECO /converter mode.
(
Note:
Before making charger output voltage adjustment, be sure to
disconnect all batteries first to get the accurate charger voltage; Be
careful that the adjustment should be suitable to battery specifica
-
tions, or the battery may be destroyed.)
Alarm Page
This page records and displays the faults or warnings event history.