XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation
Page 20
Safety Information
Information presented here is vital to all personnel. Please read all Safety information.
IMPORTANT
Before making any connection and switching on the XPRT Series UPS, please check
the following conditions:
•
All electrical connections are to be realized by qualified skilled personnel only.
•
To avoid potential health risks, electrical components should not be mechanically damaged or
destroyed. Do not touch electronic components. They may be electrostatic sensitive and are for
that reason easily damaged due to improper handling.
•
Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight. It is
important that the unit has adequate ventilation. Maintain air movement around and through the
unit. Do not block the air vents.
•
The ambient temperature should not exceed 40
°
C(104
°
F). Optimal battery lifetime is obtained if
the ambient temperature does not exceed 30
°
C (86
°
F).
•
Avoid spilling liquids or dropping any foreign object into the UPS.
•
The UPS should only be powered from a two phase, four wire AC source equipped with neutral
and earth connection. The input utility is 100 - 127 Volts (Line-N) and 60 Hz (if the input utility
frequency is 50Hz, the output frequency of the UPS can be changed).
•
The total power demand of the connected equipment does not exceed the rated output power
of the XPRT Series UPS
•
The branch circuit supply has to be protected as follows:
UPS model
Branch protection
XPRT-6000
30A slow
XPRT-10000
60A slow
CAUTION
To reduce risk of fire, connect the UPS only to a circuit provided with fuse or
circuit breaker values as shown above.