6.
Re-install the terminal cover (see FIG 35 or 36)
FIG 35 – HARDWIRE TERMINAL COVER RE-INSTALL 6KVA UPS
FIG 36 – HARDWIRE TERMINAL COVER RE-INSTALL 10KVA UPS
7.
In case of external batteries, ensure the battery cable is connected between the battery cabinet
and the UPS as shown in FIG 20 or 25.
8.
Connect utility power to the UPS.
9.
Proceed to the Quick Start section of these instructions.
If parallel-operating units will be installed, please reference that section of these instructions.
NOTE
The UPS output sockets are live soon as the UPS is connected to the input utility
power, even if the UPS has not been switched on via the front panel.
For 6kVA models an additional ground connection is required (the main ground can be removed with
the PDU). Connect the UPS case to the nearest available ground connection with an 8 AWG (10 mm
2
)
copper wire (see FIG 37).