XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation
Page 42
FIG 41 – PDU INSTALL 10KVA UPS
The UPS is now ready to be started.
STARTUP
Startup 6kVA UPS
1.
Ensure that all breakers on the UPS are off.
2.
In case external battery packs are used, switch on the battery pack circuit breaker (FIG 42).
FIG 42 – 6KVA BATTERY PACK BREAKER
3.
Ensure that the manual bypass switch on the PDU is turned to the “UPS” position (FIG 43).