XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation
Page 43
FIG 43 – 6KVA PDU BYPASS SWITCH
4.
Close all switches and breakers upstream from the UPS.
5.
Switch the INPUT CIRCUIT BREAKER placed on the rear side of the UPS to “ON” position (FIG 44).
FIG 44 – 6KVA INPUT CIRCUIT BREAKER
6.
Wait 45 seconds to allow the output voltage to stabilize.
7.
Press the keypad “UPS ON” for 1 second. Within a few seconds “OPERATION” LED will be
illuminated and “BYPASS” LED will be extinguished.
8.
Close the OUTPUT CIRCUIT BREKAER on the rear side of the UPS (FIG 45).
FIG 45 – 6KVA OUTPUT CIRCUIT BREAKER
9.
The UPS is now in operation; equipment connected to the UPS output can now be switched on.
10.
Load % will be shown on the “LOAD” LED BAR.
Startup 10kVA UPS (stand-alone not parallel systems)
1.
Ensure that all breakers on the UPS are off.
2.
In case external battery packs are used, switch on the battery pack circuit breaker (FIG 46).
FIG 46 – 10KVA BATTERY PACK BREAKER
3.
Ensure that the bypass circuit breaker on the UPS is turned to the “UPS” position (FIG 47), or
that the protection bar is still mounted.