FIG 59 – 10KVA UPS PARALLEL SYSTEM DIAGRAM EXAMPLE
3.
Use insulated copper input and output wiring, rated 90°C (194
°
F) wire size based on the ampacities
given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-1993. Specified in table 2 and
table 3.
4.
The length of all input cables from the input junction (FIG 59) to the UPS inputs should be equal.
The same applies to the cables from the outputs to the output junction (FIG 59). The minimum
length of the input as well as the output cables is 3 meters.
5.
The overall system load may not exceed 100% load of a single UPS in the configuration without the
addition of an external maintenance bypass. Optional Xtreme Power bypass panel is available to
meet this requirement. Please contact Xtreme Power Sales for additional information.