Xtreme Power Conversion® (XPC) Corporation
Page 69
3.
Loosen the 3 mounting screws of the internal battery cover and remove it (FIG 70).
4.
Loosen the 5 mounting screws of the power module cover and remove it (FIG 70).
5.
Slide the power module out of the UPS cabinet (FIG 70).
6.
Power module can now be replaced.
7.
Slide in the new power module until the rear connector of the power module is plugged into the
socket on the UPS (FIG 76).
FIG 76 – 10KVA POWER UNIT REINSTALL
8.
Reposition the power module cover and re-affix with the 5 screws (FIG 75).
9.
Re-affix the 3 front covers (FIG 75).
10.
Switch the UPS back to normal operation.
TROUBLESHOOTING
Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it and be sure that the UPS is not
overloaded.
The following chart is a simple troubleshooting checklist. If the suggested solution does not succeed, or if
the information is insufficient to solve the problem, please contact your dealer or consult
www.xpcc.com
.