XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 19
4 LEDs = 61-80%
5 LEDs = 81-100%
LED Bar Load (Green or Yellow)
These LEDs indicate to what extent the output capacity of the UPS is used by the actual load for each
output line (L1 and L2). If for example, the 25%, 50%, and 75% LEDs are on for Line 1, and the 25% and
50% LEDs are on for Line 2, the load exceeds 50% of the maximum load for Line 1 and 25% of the
maximum load for Line 2. If all 5 LEDs are on, the unit operates in overload. As this is an abnormal
situation, the alarm LED will also be on.
1 LED = 0-25% Green
2 LEDs = 26-50% Green
3 LEDs = 51-75% Green
4 LEDs = 76-100% Green
5 LEDs = >100% Yellow
Remote Emergency Power Off (EPO) Port
A customer supplied switch located remotely can be used to open the EPO connection and allows the
UPS output receptacles to be switched off. Since the EPO shuts down the equipment immediately,
orderly shutdown procedures are not followed by any power management software. The UPS will have
to be manually restarted in order to regain power to the outlets on the UPS.
HARDWARE INSTALLATION GUIDE
Inspect the UPS for damage after unpacking. If any damage is present please immediately notify the carrier
and place of purchase.
NOTE
The internal battery packs for these UPS ship separately. FOR the 6kVA model
there is 1 internal battery pack, and for the 10kVA model there are 2 internal
battery packs are shipped separately.
WARNING!
In case of recognizable damage:
DO NOT
connect any voltage to the unit
DO NOT
put the unit into operation