XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation
Page 41
FIG 38 – PDU REMOVAL 6KVA UPS
5.
On the 10kVA model, loosen the four mounting screws (FIG 39) on the PDU cover and remove it.
FIG 39 – PDU COVER REMOVAL 10KVA UPS
6.
Remove the PDU from the UPS.
The UPS is now ready for the new PDU assembly.
7.
On the 6kVA model, align terminals on the backside of the PDU with the ones on the UPS, and
slide the PDU into the UPS (FIG 40).
FIG 40 – PDU INSTALL 6KVA UPS
8.
On the 10kVA model, connect terminals on the backside of the PDU with connections in the PDU
tray on the backside of the UPS, and slide the PDU into the UPS (FIG 41).