In FAULT MODE, the UPS is “forced” on bypass or standby. After having solved the cause of the fault
condition, you have to press the UPS OFF button for 0.5 seconds to switch the UPS to normal mode or
restart the unit.
Standby
In standby mode, the UPS is turned off (output power is lost) and the batteries are being recharged. To
put the UPS in Standby, press for 1 second the UPS OFF switch, the UPS switches to bypass. Press one
more time UPS OFF switch for 1 second. The UPS is now in standby mode. Most changes to the UPS
settings are only possible in bypass or standby mode.
Remote Emergency Power Off (REPO)
REPO may be created using either normally open or normally closed switch. The unit is shipped with a
jumper connected between pin 3-4 (FIG 67). In case of connection with a normally open contact, this
jumper must be removed and a normally open switch cabling must be connected between pin 1-2 (FIG
67). In case of connection with a normally closed contact, the jumper must be shifted between pin 1-2
and the normally close switch must be connected between pin 3-4 (FIG 67).
FIG 67 – REPO JUMPER PLACEMENT
When REPO is activated the UPS will transfer to stand-by mode and output power is lost. It’s not possible to
restart the unit while the REPO is activated, thus, depending on the used switch, the connection must be