XVT

600,

 

XVT

800,

 

XVT

1200,

 

XVT

1500

 

USER’S

 

MANUAL

 

UNINTERRUPTIBLE

 

POWER

 

SUPPLY

 

(UPS)

 

 

SPECIFICATIONS

 

  

120V Model 

XVT-600 

XVT-800 

XVT-1200 

XVT-1500 

INPUT 

Voltage 

94V-144V ± 5V 

Capacity VA (W) 

600 VA (360 W) 

800 VA (480 W) 

1200 VA (720 W) 

1440 VA (900 W) 

Frequency 

60HZ ± 5Hz 

OUTPUT 

Voltage  

105-134 VAC (120V ± 12%) 

Waveform 

Pure Sine Wave (Typical) 

Frequency 

AC mode-follow utility Battery mode 60 ± 0.5Hz 

Transfer Time 

4ms (Typical) 

Surge Protection 

320 Joules 

Input Protection 

Compliance with IEEE 587 

Short Circuit 

Breaker 

BATTERY 

Battery Type 

Sealed, Maintenance-free lead acid 

Battery Qty & 
Size 

(1) 12V 7AH 

(1) 12V 9AH 

(2) 12V 7AH 

(2) 12V 9AH 

Recharge 

less than 10 hours to 90% capacity 

Backup Time 
(full load) & (half 
load) 

3 min (full load) 

 6 min (50% load) 

Charge Current 

1.5A (Max) 

PHYSICAL 

Dimensions 

W x D x H 

(inches) 

W x D x H 

(inches) 

W x D x H 

(inches) 

W x D x H 

(inches) 

Product 
Dimensions 

3.7” x 14.6” x 

6.2” 

3.7” x 14.6” x 

6.2” 

4.9” x 16.9” x 

8.7” 

4.9” x 16.9” x 

8.7” 

Shipping 
Dimensions 

6.1”x 16.2”x 

10.2” 

6.1”x 16.2”x 

10.2” 

7.5”x 18.9”x 

12.8” 

7.5”x 18.9”x 

12.8” 

Product Weight 

15.3 lbs. 

16.8 lbs. 

27.6 lbs. 

31.3 lbs. 

Shipping Weight 

17.6 lbs. 

19.2 lbs. 

29.8 lbs. 

32.4 lbs. 

Line Cord (6 ft.) 

NEMA 5-15P 

Receptacles 

(6) NEMA 5-15R (3-SURGE PROTECTED/3-UPS) 

Communication 
Interface 

USB Communications 

Bezel Color 

Brushed Metallic Outer / Black Inner 

Included in box 

PowerManager CD, USB cable, Manual 

ENVIRONMENT 

Operating 
Temperature 

0-35ºC 

Humidity 0%-90% 

Audible Noise 

<45dB 

Altitude 

5000 ft. (1500 m) above sea level 

WARRANTY 

Warranty 

Two years electronics / One year batteries 

APPROVALS 

North America 

UL cUL FCC 

 

[17]

 

Summary of Contents for XVT?1200

Page 1: ...Xtreme Value Tower Series XVT User s Installation Manual Xtreme Power Conversion Corporation ...

Page 2: ...TION 5 DETERMINING THE POWER REQUIREMENTS OF YOUR EQUIPMENT 7 HARDWARE INSTALLATION GUIDE 7 QUICKSTART SOFTWARE INSTALLATION GUIDE 9 REPLACING THE BATTERY 14 DEFINITIONS FOR LED INDICATORS 15 ALARMS 15 TROUBLESHOOTING 16 SPECIFICATIONS 17 SHIPPING LIST OBTAINING SERVICE 19 18 XTREME POWER CONVERSION XPC CORPORATION LIMITED WARRANTY 20 2 ...

Page 3: ...its for a Class B Digital Device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications There is no guarantee th...

Page 4: ...tenance No user serviceable parts inside CAUTION Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected CAUTION UPS must be connected to an AC power outlet with fuse or circuit breaker protection Do not plug into an AC wall outlet that is not grounded If you need to de energize this equipment turn off and unplug the UPS DO NOT USE FOR MEDICAL OR LI...

Page 5: ... Interactive Automatic Voltage Regulation AVR UPS technology Under normal AC power operation the input power flows through the AVR circuit regulating the incoming AC power to the output of the UPS and the load connected If the input power disappears the Inverter circuit is switched on to provide output from the batteries contained within the UPS 5 ...

Page 6: ...ing a power failure Power Switch Can be used as a master on off switch for equipment connected to the battery powered outlets Power On Indicator This LED is illuminated when the utility condition is normal and the UPS outlets are providing power free of surges and spikes Circuit Breaker The circuit breaker that provides overload and fault protection USB Port protocol that provides communication be...

Page 7: ...actors can affect the amount of power that your computer system will require The total load that you will be placing on the battery powered outlets should not exceed 85 of the UPS capacity HARDWARE INSTALLATION GUIDE 1 Your new UPS may be used immediately upon receipt however charging the battery for at least 4 hours is recommended to ensure that the batteries maximum charge capacity is achieved C...

Page 8: ...he UPS on 6 Your UPS is equipped with an auto charge feature When the UPS is plugged into an AC wall outlet and there is acceptable AC voltage present the battery will automatically recharge Charging is controlled by firmware to rapidly charge units to 15VDC 600 800VA units and 29VDC 1200 1500VA units After this threshold is met the XVT places a float charge to maintain battery energy and the char...

Page 9: ...ide the box 2 Insert one end of the USB Cable into the UPS and the other into a USB port on your computer 3 Insert the CD into your computers CD drive 4 When the software interface requests a serial number locate and input the serial number from the CD software jacket 5 Follow the software setup prompts 6 Quickstart Software Installation Guide 9 ...

Page 10: ...VT 1500 USER S MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Input user name company name and serial number into the software interface Note the serial number is on the CD software jacket Choose installation location and click Next 10 ...

Page 11: ...XVT 600 XVT 800 XVT 1200 XVT 1500 USER S MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Choose software language and click Next Software will install automatically 11 ...

Page 12: ... XVT 1200 XVT 1500 USER S MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Choose Will you run Powermanager II right now and click Finish After the UPS switches on please choose the System Setting tab from the drop down box 12 ...

Page 13: ...XVT 600 XVT 800 XVT 1200 XVT 1500 USER S MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS Click Local UPS and choose USB click OK The UPS is now connected and in normal operation 13 ...

Page 14: ...tem voltage is only 12VDC and 24VDC the battery can present a high risk of short circuit current and electrical shock The short circuit current capability of the battery is sufficient to burn wire or tools very rapidly producing molten metal Observe these precautions when replacing the battery 1 Remove all watches rings or other metal objects 2 Only use tools with insulated handles 3 Do not lay to...

Page 15: ... Power OFF OFF FLASH On Battery ON Charge ON Overheat Low Battery Overload Protection Short Circuit Note means any situation ALARMS Alarm Indication Unit Status Buzzer every 5 sec DC start Buzzer every 1 sec Self test 2 buzzer every 1 sec Low battery 4 beep every 2 4 sec Overload 3 buzzer every 1 sec Overheat Input is off long beep power off after 5 sec Short circuit 15 ...

Page 16: ...least 4 hours The battery is defective Contact Xtreme Power Conversion about replacement of batteries The UPS will not turn on The on off switch is designed to prevent damage by rapidly turning it off and on Turn the UPS off Wait 10 sec then turn the UPS on The UPS is not plugged into an AC wall outlet Connect the UPS to an 110 120V 60Hz AC wall outlet The battery is defective Contact Xtreme Power...

Page 17: ...l load half load 3 min full load 6 min 50 load Charge Current 1 5A Max PHYSICAL Dimensions W x D x H inches W x D x H inches W x D x H inches W x D x H inches Product Dimensions 3 7 x 14 6 x 6 2 3 7 x 14 6 x 6 2 4 9 x 16 9 x 8 7 4 9 x 16 9 x 8 7 Shipping Dimensions 6 1 x 16 2 x 10 2 6 1 x 16 2 x 10 2 7 5 x 18 9 x 12 8 7 5 x 18 9 x 12 8 Product Weight 15 3 lbs 16 8 lbs 27 6 lbs 31 3 lbs Shipping We...

Page 18: ...Mode Green LED on Orange LED on Red LED off no beep Charging Battery Orange LED on Battery Mode Green LED and Orange LED off Red LED flash buzzer slow beep Battery Low Green LED and Orange LED off Red LED on buzzer fast beep SHIPPING LIST 1 1 UPS 2 1 User s and Installation Manual 3 1 Intelligent monitoring software 4 1 USB computer port cable 18 ...

Page 19: ...nician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Material Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer availa...

Page 20: ... a the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifications or c the equipment has been used or stored in a manner contrary to the equipment s operating...

Page 21: ...XVT 600 XVT 800 XVT 1200 XVT 1500 USER S MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS 21 ...