R90 ONLINE USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion Corporation (Rev 3/7/14)
Page 51
Parallel ID setting
PARALLEL ID SETTING
(Note: the information in the red box will be flashing)
When in bypass voltage lower limit setting press On
or when in parallel quantity setting press Off
to go to the parallel ID setting mode. The parallel ID line flashes as in the above image. Use the Enter
button to choose different parallel ID. Parallel ID range is 1 - 4. Press Off
or On
to exit the parallel
ID setting (save the parallel ID setting), and then goes to bypass voltage lower limit setting or parallel
quantity setting.
CAUTION!
Parallel cable cannot be connected when setting the parallel parameters
Note:
If installing 5-6 units in parallel, remove the jumper cap J30 on the control inspection board
(MHTBJHR1CU04 in all UPS to be connected in parallel.
If installing 7-10 units in parallel, remove the jumper cap J30/J31 on the control inspection
board (MHTBJHR1CU04 in all UPS to be connected in parallel.