R90 ONLINE USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion Corporation (Rev 3/7/14)
Page 53
Parallel redundancy quantity setting
PARALLEL REDUNDANCY QUANTITY SETTING
(Note: the information in the red box will be flashing)
When in parallel quantity setting, press On
to go to the parallel redundancy quantity setting mode.
The parallel redundancy quantity line flashes as in the above image. Use the Enter
button to choose
different parallel redundancy quantity. Parallel redundancy quantity range is 0 - 3. Press Off
or On
to exit the parallel redundancy quantity setting (save the parallel redundancy quantity setting), and then
goes to parallel redundancy setting or to exit the mode setting. The UPS LCD panel setting is now
completed.
CAUTION!
Parallel cable cannot be connected when setting the parallel parameters
Note:
If installing 5-6 units in parallel, remove the jumper cap J30 on the control inspection board
(MHTBJHR1CU04 in all UPS to be connected in parallel.
If installing 7-10 units in parallel, remove the jumper cap J30/J31 on the control inspection
board (MHTBJHR1CU04 in all UPS to be connected in parallel.