Xtreme Power Conversion Corporation

C60 User’s Manual

Page 7

Uninterruptible Power Supply

Specifications

MODEL NUMBER

C60‐800

C60i‐800

INPUT

Capacity

800VA (480W)

Nominal voltage

120VAC

230VAC

Voltage range

80–135VAC 

± 5%

175–254VAC

Frequency range

55–65Hz at 60Hz ± 1Hz

45–55Hz at 50Hz ± 1Hz

Surge protection

158 J

AC power cord

6 ft, IEC C13 to 5–15P

IEC C14 inlet only

OUTPUT

Voltage (line mode)

80–135VAC 

± 5%

175–254VAC

Voltage (battery mode)

120VAC ± 10%

230VAC 

± 10%

Voltage regulation

± 2%

Frequency (line mode)

55–65Hz at 60Hz ± 1Hz

45–55Hz at 50Hz ± 1Hz

Frequency (battery mode)

60Hz ± 1Hz

50Hz ± 1Hz

Waveform

Sine wave (normal), simulated sine wave (battery mode)

Transfer time

2–6 ms

Outlets

(2) NEMA 5–15R

(2) IEC C13

Overload capacity

110% +20% / ‐10% for 5 min; 120% +20% / ‐10% immediately off

Efficiency

> 95%

BATTERY

UPS battery type

(1) 12V 9AH / 12VDC

UPS charge current

1A maximum

Recharge time

8 hours to 90% capacity

PHYSICAL

Dimensions (W x D x H)

4.0 x 13.0 x 5.7 in

Weight

7.5 lbs

ENVIRONMENT

Temperature

32–104

°

F (0–40

°

C)

Humidity

0–90%

Altitude

11,500 ft above sea level

INDICATORS &

Line mode

Green LED illuminated

ALARMS

Battery mode

Green LED flashing every 10 sec

Battery low

Green LED flashing every 1 sec

Fault mode

Off

Audible alarm

Battery mode ‐ every 10 sec; low battery ‐ every 1 sec; overload ‐ ever 0.5 sec; 

fault ‐ constant alarm

APPROVALS

UL 1778, FCC Class A, RoHS

S‐Mark, EN62040‐1, EN62040‐2, RoHs

WARRANTY

3 years electronics, 3 years battery (USA and Canada)

Summary of Contents for C60-800

Page 1: ...60 Standby UPS 800VA Models User Installation Manual 2015 Xtreme Power Conversion Corporation All rights reserved Rev 6 23 15 For more information visit www 247technology com on line ups c60 standby ups ...

Page 2: ...ninterruptible Power Supply Table of Contents Package Contents 3 ProductIntroduction 3 Product Overview 3 Installation Initial Startup 4 Indicators Alarm Conditions 5 Troubleshooting 6 Specifications 7 Obtaining Service 8 Xtreme Power Conversion Limited Warranty 9 ...

Page 3: ... set up your system for the maximum safety and performance Included is information on customer support and service if it is required If you experience a problem with the UPS please refer to the Troubleshooting section in this manual to correct the problem If the problem is not corrected please collect in formation so that the Technical Support personnel can more effectively assist you Product Over...

Page 4: ... on the front of the UPS For best results the batteries in the UPS should be charged for at least 8 hours before use The UPS charges its battery while it is connected to AC utility power and powered on Connecting the Loads Plug the loads to be supported by the UPS into the output receptacles on the rear of the UPS Simply turn the power switch on the UPS on and the devices connected to the UPS will...

Page 5: ...ric shock and high short circuit current The following precaution should be observed when working on batteries Remove watches rings or other metal objects Use tools with insulated handles To reduce the risk of electric shock disconnect the UPS from the main supply before installing a computer inter face signal cable Reconnect the power cord only after signaling interconnections have been made Serv...

Page 6: ...d Remove some of the load from the output of the UPS UPS fault Return the unit for service Alarm sounds every 2 seconds when the AC input is normal Battery defect Replace the battery with the same type of battery Charging circuit is damaged Return the unit for service When power fails backup time is shorter than expected The UPS is overloaded Remove some of the load from the output of the UPS Batt...

Page 7: ...ated sine wave battery mode Transfer time 2 6 ms Outlets 2 NEMA 5 15R 2 IEC C13 Overload capacity 110 20 10 for 5 min 120 20 10 immediately off Efficiency 95 BATTERY UPS battery type 1 12V 9AH 12VDC UPS charge current 1A maximum Recharge time 8 hours to 90 capacity PHYSICAL Dimensions W x D x H 4 0 x 13 0 x 5 7 in Weight 7 5 lbs ENVIRONMENT Temperature 32 104 F 0 40 C Humidity 0 90 Altitude 11 500...

Page 8: ...sk you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available ask the ...

Page 9: ...PC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifi cations or c the equipment has been used or stored in a manner contrary to the equipment s operating manual intended use or other written instructions Any technical advice furnished b...

Reviews: