Uninterruptible Power Supply
SYS PARAMETER
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
85211810100018000
----------------
Model Name
INITIAL
Serial Number
10
12A
Manufacturer
Max Charge CURR
BATT Number
Charger Number
3PCS
SYS Parameter Page1
• Mode Name: Set the UPS model name.
• Serial Number: Set the serial number.
• Manufacturer: Set the UPS manufacturer.
• Charger Number: The number of charging boards installed in the UPS.
NOTE: It’s required to restart the UPS after setting. The setting for 15K to 40K only.
One charger board: When selected, there are four options available for “Max Charge CURR”.
Two charger boards: When selected, there are two options available for “Max Charge CURR”.
Three charger boards: When selected, there are three options available for “Max Charge CURR”.
• Max Charge CURR: The maximum of battery charging current. This parameter setting is related to
“Charger Number” setting.
If UPS is 15K or 20K, the selectable charge current is listed below.
One charger board: There are four options, 1A, 2A, 3A, 4A. 4A is default setting.
Two charger boards: There are two options, 4A and 8A. 4A is default setting.
Three charger boards: There are three options, 4A, 8A, 12A. 4A is default setting.
Four charger boards: There are four options, 4A, 8A, 12A, 16A. 4A is default setting. (Only for
15K and 20K)
Five charger boards: There are five options, 4A, 8A, 12A, 16A, 20A. 4A is default setting. (Only
15K and 20K)
If UPS is 30K or 40K, the selectable charge current is listed below.
• One pairs of charger boards: There are four options, 2A, 4A, 6A, 8A. 8A is default setting.
• Two pairs of charger boards: There are two options, 8A, 16A. 8A is default setting.
• Three pairs of charger boards: There are three options, 8A, 16A, 24A. 8A is default setting.
If UPS is 10K, it only has a charging board.
• The charging current is from 1A to 12A. 4A is default setting.
• BATT Number: The total number of installed battery. (UPS should be restarted after setting.) The
setting range is 8 ~ 10. 10 is default setting.
• Float VOL: The setting point of battery float voltage. 13.6V is default setting.
• UPS Type: There are two options, HV and LV. This change is only allowed for qualified technician.
NOTE: It’s required to restart the UPS after setting.