9. Verify that the
LED is illuminated solid, indicating that the UPS is operating normally and any loads are
powered.
10.
If optional EBPs are installed, see “Configuring Battery Settings” section in this manual to set the number
of installed EBPs.
11.
To change any other factory-set defaults, see “User Settings” section in this manual.
Note:
At initial startup, the UPS sets system frequency according to the input line frequency (input frequency auto-
sensing is enabled by default).
Note:
At initial startup, please set the output voltage needed before startup of the UPS. After the subsequent
startup, the UPS will output the setting voltage.
12.
If you installed an optional EPO, test the EPO function: Activate the external EPO switch. Verify the status
change on the UPS front panel display. Deactivate the external EPO switch and restart the UPS.
Note:
The internal batteries charge to 80% capacity in less than 5 hours. However, it is recommended that the bat-
teries should be charged for 48 hours after installation or long-term storage. If optional EBPs are installed, see the
recharge times listed in this manual.