Uninterruptible Power Supply
WARNING!
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes.
It may be toxic.
CAUTION!
Do not discard the battery pack or the batteries in the trash. This product contains sealed, lead-acid
batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous
waste center.
CAUTION!
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal , con-
tact your local recycling/reuse or hazardous waste center.
Specifications
Internal Batteries
EBPs
Tower Configuration
1K -EBP: 36 Vdc (2 x 3 ,12V, 7 Ah)
2K -EBP: 72 Vdc (2 x 6 ,12V, 7 Ah)
3K -EBP: 72 Vdc (2 x 6 ,12V, 9 Ah)
Fuses
30A/250 Vdc fuses per EBP
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3 year
float service life at 25°C (77°F)
Monitoring
Advanced monitoring for earlier failure detection and warning
Recharge Time (to 90%)
Internal batteries: 3 hours 1 EBP: 9 hours; 2 EBPs : 15 hours; 3 EBPs: 21 hours;
4 EBPs: 27 hours