Xtreme Power Conversion Corporation
M90U-80 & 140 User’s Manual
Page 23
Uninterruptible Power Supply
2.11.3 External Battery Cabinet Connection
Figure 2-24 External Battery Cabinet Wiring
After the battery is completely installed, be sure to set up nominal battery voltage, battery capacity and maximum
charging current in LCD setting. Otherwise, if battery setting is different from actual installation, the UPS will keep
warning. Please refer to section 4.2.6.3 and Table 4-9 for the details.
2.12 Power Module Installation
The weight of Power Module is over 70lbs.
2.12.1 Insert the Power Module
1. Adjust the DIP switch positions to set the different Module Address. Refer to Table 2-1.
2. Place the ready switch at the front panel of the module to the “ ” position (i.e., in unready state).
3. Insert the Power Module into an unoccupied slot by using two persons.
UPS