Xtreme Power Conversion Corporation
M90U-80 & 140 User’s Manual
Page 31
Uninterruptible Power Supply
The operating procedures are as follows:
Step 1:
Refer to “Chapter 2 Installation” to connect the power cables and install the Power Modules and the bat
-
tery required for the UPS system.
Step 2:
Switch ON the battery breaker.
Step 3:
Switch ON the external power switch in distribution panel to power the UPS. The STS module is powered
up and the LCD panel is displayed.
Step 4:
Switch ON the input breaker (Q1). The UPS will enter into Standby Mode, if the setting of Bypass mode is
disabled.
Or the UPS will enter into Bypass Mode, if the setting of Bypass mode is enabled.