Xtreme Power Conversion Corporation
M90U-80 & 140 User’s Manual
Page 52
Uninterruptible Power Supply
Figure 4-16 Warning screen
Table 4-8:
Setup-System setting list
Setting Item
Sub Item
Explanation
Output Voltage
--
Set output voltage
• 120Vac (Default)
•
127Vac
MUST be reviewed after UPS installation
BYPASS SETTING
Voltage
Set bypass voltage range:
Upper limit
• +10%
• +15% (Default)
• +20%
Lower limit
• -10%
• -20% (Default)
• -30%
Frequency
Set bypass Frequency range:
Upper/ Lower limit
• +/- 1Hz
• +/- 2Hz
• +/- 4Hz (Default)
Converter Mode
--
Set converter mode
• Disable (Default)
• Enable
ECO Mode
--
Set ECO mode
• Disable (Default)
• Enable
Bypass Mode
--
Set bypass mode
• Disable (Default)
• Enable
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please enable it.