Xtreme Power Conversion Corporation
M90U-80 & 140 User’s Manual
Page 72
Uninterruptible Power Supply
M90U-80 Specifications
*Depending on load level **Battery life is reduced above 30°C, UPS capacity derates above 30°C and 5,200 ft above sea level
MODEL NUMBER
M90U80-20k
M90U80-40k
M90U80-60k
M90U80-80k
CAPACITY
Power rating
20kVA/20kW
40kVA/40kW
60kVA/60kW
80kVA/80kW
Enclosure capacity: power modules
Up to 80KVA (4 x 20KVA) or up to 60kVA (4 x 15KVA)
Enclosure capacity: battery mod
-
ules
4, 8, 12, or 16 internal battery modules
INPUT
Voltage / frequency nominal
208/120V, 50/60Hz auto-sensing
Voltage / frequency range
121–253VAC*
(L-L)
, 40–70Hz
OUTPUT
Voltage
208/120V
Frequency
50/60Hz ± 0.5Hz
THD (full load)
< 2%
Efficiency
Up to 94% online mode or 98% ECO mode
Overload capacity
105%-110% for 60min; 110%-125% for 10min; 126%-150% for 1min; >150% for
200ms
BATTERY SYSTEM Nominal voltage
± 120V
Charge Current (programable)
8A
16A
24A
32A
DIMENSIONS & Enclosure
23.6"W x 43.3"D x 79.1"H / 657 lbs
WEIGHT
Power module
19.5”W x 29.5”D x 5.5”H / 74 lbs
Battery module
4.3”W x 28.5”D x 6.5”H / 70 lbs
ENVIRONMENT Temperature
0–40°C (32–104°F)**
Altitude
5,200 ft above sea level**
Audible noise
< 65dBA at 1m
APPROVALS
UL-1778 (TUV), cUL (TUV), FCC A, RoHS, TAA
WARRANTY
2 years (USA and Canada)
COMMUNICATIONS INTERFACE
RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus)
INCLUDED IN BOX
User manual, RS-232 cable, unloading ramp, ViewPower Software
AVAILABLE OPTIONS
External maintenance bypass, 480V input transformer, output distribution,
battery temperature sensor