Xtreme Power Conversion Corporation
P90L 6kVA & 10kVA User’s Manual
Page 48
Uninterruptible Power Supply
P90L-ISO6MB Output Terminal Block
P90L-ISO10MB Output Terminal Block
The drawing shown above is the default configuration. Jumpers are pre-installed for this configuration internally
for 6kVA only. 10kVA jumpers are to be made in the field (shown below).
Contact Technical Support for additional voltage configurations if needed.
P90L-ISO6MB Internal Jumper
P90L-ISO10MB Internal Jumper
Connect Maintenance Bypass Switch communication cable (C1) from RJ45 port on P90L-ISO6MB or P90L-ISO10MB
to green molex connector on UPS. This prevents UPS damage should it not be in bypass prior to activating Mainte
-
nance Bypass Switch on P90L-ISO6MB or P90L-ISO10MB