Xtreme Power Conversion Corporation
T90 User’s Manual
Page 21
Uninterruptible Power Supply
Technical Specifications
MODEL NUMBER
T90-700
T90-1000
T90-1500
*
T90-2000
T90-3000
T90i-1500
INPUT
Capacity
700VA (490W) 1000VA (700W) 1500VA (1050W) 2000VA (1400W) 3000VA (2100W) 1500VA (1050W)
Voltage range
60–144VAC**
120–276VAC**
Frequency
50/60Hz auto sensing
OUTPUT
Voltage
120VAC nominal (100/110/115/127VAC selectable)***
208/220/
230/240VAC
Waveform
Sine wave, zero transfer time
Frequency
50/60Hz auto sensing ≤ 1%
Load segments
Two controlled via software
Load power factor
0.7
Efficiency
High efficiency > 95%, normal mode > 90%
Overload capacity
125% for 1 min, 150% for 10 sec
BATTERY
Battery type
(2) 12V 7.2AH
(3) 12V 7.2AH
(3) 12V 9AH
(6) 12V 7.2AH
(6) 12V 9AH
(3) 12V 9AH
Recharge
4 hours to 90% capacity
PHYSICAL
UPS dimensions
6.0 x 16.5 x 9.5 in
8.9 x 16.5 x 14.2 in
6.0 x 16.5 x 9.5 in
(W x D x H)
UPS weight
31 lbs
38 lbs
39 lbs
73 lbs
78 lbs
39 lbs
Line cord
5–15P*
5–20P
L5–30P
IEC C14 inlet
Receptacles
(6) NEMA 5–15R*
(12) NEMA
5–15/20R
(10) NEMA
5–15R
(4) IEC C13
+ (1) L5–30R
LCD display
Input/output voltage, input/output frequency, online mode, backup mode, battery capacity, load level
OPTIONAL
Model number
N/A
T90-BP/T90-BP1
T90-BP2
T90-BP/T90-BP1
BATTERY PACKS
Dimensions
N/A
BP – 6.0 x 16.5 x 9.5 in; BP1/BP2 – 8.9 x 16.7 x 14.2 in
(W x D x H)
Weight
N/A
BP = 46 lbs; BP1/BP2 = 88 lbs
Battery type
N/A
T90-BP – 2 x (3) 12V 7.2AH; T90-BP1 – 4 x (3) 12V 7.2AH; T90-BP2 – 2 x (6) 12V 7.2AH
ENVIRONMENT Temperature
32–104°F (0–40°C)
Audible noise
< 40 dBA
Altitude
11,500 ft above sea level
APPROVALS
UL, cUL, FCC, CE
WARRANTY
3 years electronics, 3 years battery warranty (USA and Canada)
COMMUNICATIONS INTERFACE
RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP, Relay/dry contact)
INCLUDED IN BOX
User manual, monitoring software, CD, USB cable
AVAILABLE OPTIONS
Extended warranty, bypass distribution (XBDM), power distribution (XPDU)
*T90-15HW 1500VA model available with input and output terminal blocks
**Depending on load level
***T90 capacity derates 10% at 110VAC and 20% at 100VAC output voltage