Uninterruptible Power Supply
p. UPS Output Fuse: When the UPS is overloaded, the fuse will open.
q. UPS Output EMI Filter: To eliminate the magnetic interference from the UPS Output and avoid the interference
caused by the output load and the UPS.
r. CAM Switch(Maintenance Bypass Switch): Through this switch, the output load can be supplied by Bypass
Source, so a routine maintenance job can be proceeded without interruption of the systems connected to the
output.
s. UPS Isolation Transformer:
t. Communication: RS232 serial port & RJ45 parallel port with CAN technology.
u. Optional Slots: for variety use of interfaces provided such as SNMP card, 2nd RS232, USB, Relay Contact Board,
etc.
v. Optional Interface Boards: WEB/SNMP card, Dry Contact Board, RS485 card, USB card, 2nd RS232 card, etc.
w. Remote Control Box: To provide remote monitoring and control functions.
Unit Wiring Diagram
MSII series PCB boards. Please find the description as below:
Item
Description
Part No.
Function
1
Control
MSDI0XX
To generate all control signals and also AC/DC detecting
signals.
2
Power(Driver)
MSDD0XX
AC/DC, DC/DC, AC/AC and circuit working power supply.
MSED0XX
MSED5XX
AC/DC Rectify module
MSFD5XX
MSFD6XX
AC/DC, DC/DC, AC/AC and circuit working power supply.
3
EPO
MSXN0XX
Emergency Power Off
4
LCD Display
MSDM0XX
MSDM3XX
To control and display UPS Status and values
5
Charger
MSDC0XX
Battery Charger
6
I/P EMI filter
MSDF4XX
UPS Input noise filtering and surge protection
MSEF4XX
MSEF5XX
7
O/P EMI filter
MSDF0XX
UPS Output noise filtering
MSEF0XX
MSFF3XX
8
DC Capacitor
MSEB0XX
DC Energy for Inverter
MSFB0XX
9
Relay
MSEK0XX
Suppress inrush current from isolated transformer
10
Fuse or Terminal
MSEZ2XX
Protect output device or Terminal for power connection