3.3.4 Turn off Operation
3.3.4.1 Turn Off Operation in Bypass Mode/ Standby Mode
When the inverter is turned off, the UPS operates in the Standby Mode or Bypass Mode. It depends
on t
he “Bypass Mode” Setting.
The LCD screens are shown below.
Bypass Mode Setting is Disabled
Bypass Mode Setting is Enabled
Step 1
: Switch OFF the Main Breaker. The LCD screens are shown below.
Bypass Mode Setting is Disabled
UPS enters Shutdown Mode.
It is normal that
“
Un-Connection
”
is shown
when Power Modules have shut off their
control power.
Bypass Mode Setting is Enabled