Table 4-4
: Measurement item list
Menu Item
Explanation
Input
L-N Voltage (V)
Input phase voltage (L1, L2, L3), accuracy: 0.1V
Frequency (Hz)
Input Frequency (L1, L2, L3), accuracy: 0.1Hz
Output
L-N Voltage (V)
Output phase voltage (L1, L2, L3), accuracy: 0.1V
L-N Current (A)
Output phase current (L1, L2, L3), accuracy: 0.1A
Frequency (Hz)
Output Frequency (L1, L2, L3), accuracy: 0.1Hz
Power Factor
Output Power Factor (L1, L2, L3)
Bypass
L-N Voltage (V)
Bypass phase voltage (L1, L2, L3), accuracy: 0.1V
Frequency (Hz)
Bypass Frequency (L1, L2, L3) , accuracy: 0.1Hz
Power Factor
Bypass Power Factor (L1, L2, L3)
Load
Sout (KVA)
Apparent power, accuracy: 0.1KVA
Pout (KW)
Active power, accuracy: 0.1KW
Load Level (%)
The percentage of the UPS rated load, accuracy: 1%
Battery
Positive Voltage (V) Battery Positive half string voltage, accuracy: 0.1V
Negative Voltage (V) Battery Negative half string voltage, accuracy: 0.1V
Positive Current (A) Battery Positive half string current, accuracy: 0.1A
Negative Current (A) Battery Negative half string current, accuracy: 0.1A
Remain Time (Sec) Remaining Battery run time, accuracy: 1sec
Capacity (%)
The percentage of remaining battery capacity, accuracy: 1%
Test Result
Battery test result
Charging Status
Battery charging status
Temperature1(
℃
)
Battery cabinet temperature, accuracy: 0.1
℃
4.2.6 Setup Screen
Touch the
icon and the user will need to enter a password to access General, SYSTEM,
BATTERY and PRE-ALARM sub-menus as shown in Figure 4-11 and 4-12.
Figure 4-11 Setup menu
Touch the grey box and the number keyboard will pop up. Please enter 4-digit password and touch
icon to enter SETUP sub-menu. If an incorrect password is entered, the LCD screen will ask
for retry.
Summary of Contents for X90-2S
Page 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Page 15: ...Figure 2 13 Terminal Blocks...
Page 17: ...Off There is neither a fault nor an alarm...
Page 22: ......
Page 37: ......
Page 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Page 42: ......
Page 53: ...Figure 4 6 Control screen page...
Page 55: ...Figure 4 9 System Measurement Screens...
Page 56: ...Figure 4 10 Module Measurement Screens...
Page 88: ......