+10%
⚫
+15%
⚫
+20% (Default)
Lower limit
⚫
-10%
⚫
-20%
⚫
-30% (Default)
Bypass Frequency
Range
Set bypass Frequency range:
Upper/ Lower limit
⚫
+/- 1Hz
⚫
+/- 2Hz
⚫
+/- 4Hz (Default)
Converter
Mode
--
Set converter mode
⚫
Disable (Default)
⚫
Enable
⚫
50Hz
⚫
60Hz
⚫
AUTO
ECO Mode
--
Set ECO mode
⚫
Disable (Default)
⚫
Enable
Bypass
Mode
--
Set bypass mode
⚫
Disable
⚫
Enable (Default)
MUST be reviewed after UPS installation.
If you need the UPS to power the load when the inverter
is OFF, this setting must be set to
“
Enable
”
.
Auto-Restart --
Set auto-restart
⚫
Disable
⚫
Enable (Default)
If set to
“Enable”
, the UPS will enter line mode once
utility restores after the UPS has shut down upon full
battery discharge.
Power Walk
in
Set power walk in upper/lower limits
⚫
+/- 1s time step (setting range: 1s ~ 10s)
Battery
Mode Delay
Time
--
Set system shutdown delay time in battery mode
(0~990min).
⚫
0: Disable (Default)
⚫
Not 0: Enable
If set to
“
Enable
”
, UPS will shut off output after UPS
operates in Battery mode for the preset number of
minutes.
Shutdown/
Restore
System Shutdown
Time
Set system shutdown delay time (0.2~99min)
⚫
0.2 min (Default)
The delay timer will start counting when the
CONTROL-Shutdown Restore command is executed.
System Restore Time Set system restore time (0~9999min)
⚫
1 min (Default)
Summary of Contents for X90-2S
Page 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Page 15: ...Figure 2 13 Terminal Blocks...
Page 17: ...Off There is neither a fault nor an alarm...
Page 22: ......
Page 37: ......
Page 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Page 42: ......
Page 53: ...Figure 4 6 Control screen page...
Page 55: ...Figure 4 9 System Measurement Screens...
Page 56: ...Figure 4 10 Module Measurement Screens...
Page 88: ......