Overload
%
105%~110% for 60min
110%~125% for 10min
126%~150% for 1min
>150% for 200ms
Steady state voltage stability %
±1 (balanced load), ±2 (100% unbalanced load)
Total harmonic voltage
%
<2 (linear load), <4 (non-linear load)
Synchronization window
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)
Output rated current
(480V)
A
140kVA/140kW
168
8.7 Electrical Characteristics (Bypass Mains Input)
Table 8-7
: Bypass mains input
Rated power (kVA)
Unit 140
Rated AC voltage1
Vac 480 (Three-phase three-wire)
Overload
%
105%~110% for 60min
110%~125% for 10min
126%~150% for 1min
>150% for 200ms
Upstream protection, bypass
line
N/A Circuit breaker, rated up to 100% of nominal output
current.
Frequency
Hz
50/60 Auto Select
Transfer time (between bypass
and inverter)
ms
Line
→
Battery 0ms
Inverter
→
Bypass 0ms
(When phase lock fails, <4ms interruption occurs from inverter to bypass)
Inverter
→
ECO ≤
10ms
Bypass voltage tolerance
%Vac Upper limit: +10, +15 or +20, default: +15
Lower limit: -10, -20, -30 default: -20
Frequency Range
Hz
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)
Summary of Contents for X90-2S
Page 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Page 15: ...Figure 2 13 Terminal Blocks...
Page 17: ...Off There is neither a fault nor an alarm...
Page 22: ......
Page 37: ......
Page 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Page 42: ......
Page 53: ...Figure 4 6 Control screen page...
Page 55: ...Figure 4 9 System Measurement Screens...
Page 56: ...Figure 4 10 Module Measurement Screens...
Page 88: ......