2.8 Control Panel
2.8.1 LCD Display
The touch screen color LCD display shows the UPS
’
operation mode. In addition, a user can also
view measurement, parameters, versions of firmware, warnings and etc. on the LCD, as well as
controlling the UPS and setting various parameters. For detailed information, please refer to
Chapter 4.
Figure 2-14 Control Panel
2.8.2 LED Indicators
LED
Color
Status
Definition
LINE
Green
On
Input source is normal.
Flashing
Main Input source is abnormal.
Off
No input source
BYPASS
Yellow
On
Load on Bypass
Flashing
Bypass Input source is abnormal.
Off
Bypass circuit is not operating.
LOAD
Green
On
The UPS is outputting power to the load.
Off
The UPS is not outputting power to the load.
INV
Green
On
Load on inverters
Off
Inverter circuit is not operating.
BATTERY
Red
On
UPS is in battery mode.
Flashing
Battery voltage is low.
Off
UPS isn
’
t in battery mode and battery is fully charged.
FAULT/
ALARM
Red
On
UPS fault
Flashing
UPS alarm