3.3.2 Cold Start Startup
Step 1
: Switch ON the battery Breaker.
Step 2
: Press the
“
Battery
Start” button
on any one of Power Modules to start up the control
power of all Power modules and STS moodule as shown below.
Step 3
: After pressing
the “Battery
Start
”
button, UPS will enter into Standby mode. Refer to the
diagram below for LCD display.
Step 4
: Before UPS enters into shutd
own mode, please press “P
OWER
” button for 2 second
s
immediately as shown in the diagram below.