40
Step 5:
Then, UPS will enter Battery Mode as shown in the diagram below.
Step 6:
Switch ON the output breaker (Q3). Cold start startup procedure is complete.
3.3.3 Maintenance Bypass Operation
Follow the instructions to transfer to Maintenance Bypass and UPS protection as below. Breaker
references below are for XPC provided XPC-SMB350 and seven hundred bypasses. Refer to your
specific external bypasses for specific references to your bypass for all others.
3.3.3.1 Transfer to maintenance bypass
Step 1
:
Remove the mechanical lock plate of
Maintenance Bypass Breaker.
Step 2
Make sure the UPS operates in Bypass mode
as shown below.