60
Setup-System setting list is shown in
Table 4-8
.
Table 4-8
: Setup-System setting list
Setting Item Sub Item
Explanation
Output
Voltage
--
Set output voltage
⚫
480Vac (Default)
MUST be reviewed after UPS installation
BYPASS
SETTING
Bypass Voltage Range
Set bypass voltage range:
Upper limit
⚫
+15% (Default)
Lower limit
⚫
-10%
⚫
-20% (Default)
⚫
-30%
Bypass Frequency
Range
Set bypass Frequency range:
Upper/ Lower limit
⚫
+/- 1Hz
⚫
+/- 2Hz
⚫
+/- 4Hz (Default)
Converter
Mode
--
Set converter mode
⚫
Disable (Default)
⚫
Enable
⚫
50Hz
⚫
60Hz
⚫
AUTO
ECO Mode
--
Set ECO mode
⚫
Disable (Default)
⚫
Enable
Bypass
Mode
--
Set bypass mode
⚫
Disable
⚫
Enable (Default)
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please
enable it.
Auto-Restart --
Set auto-restart
⚫
Disable
⚫
Enable (Default)
After “Enable” is set, once UPS shutdown occu
rs due to
low battery and then utility restores, the UPS will return
to line mode.
Power Walk
in
Set power walk in upper/lower limits
⚫
+/- 1s time step (setting range: 1s ~ 10s)
Battery
Mode Delay
Time
--
Set system shutdown delay time in battery mode
(0~990min).
⚫
0: Disable (Default)
⚫
Not 0: Enable
When this feature is enabled, UPS will shut off output
after UPS operates in Battery mode for certain minute.
Shutdown/
Restore
System Shutdown
Time
Set system shutdown time (0.2~99min)
⚫
0.2 min (Default)