8.5 Electrical Characteristics (Intermediate DC Circuit)
Table 8-5
: Battery
Intermediate DC circuit
Battery
External battery
Number of lead-acid
cells
Nominal
216 (6cells x 36 12V battery block)
Maximum
240 (6cells x 40 12V battery block)
Minimum
192 (6cells x 32 12V battery block)
Float voltage
V/cell
2.28V/cell
Temperature
compensation
mV/
℃
/cl 0~-5 (adjustable)
Boost voltage
VRLA
2.35V/cell
EOD voltage
V/cell
1.783V/cell default
Battery charge
V/cell
Constant current and constant voltage charge mode
Battery charging
power
1
max
current
A
18A / per power module (adjustable)
Note
:
1.
At low input voltage the UPS recharging capability increases and load decreases (up
to the maximum capacity indicated).
2.
For 70kW module, recommend 240V battery voltage installed. Output power
wattage is 80% of rated power at 192V battery voltage. 90% of rated power at
216V battery voltage.
8.6 Electrical Characteristics (Inverter Output)
Table 8-6:
Inverter output (to critical load)
Rated power (kVA)
Unit
5
0 ~ 700
Rated AC voltage
1
Vac
480 (three-phase three -wire, L-L, without neutral)
Frequency
Hz
50/60 Auto Selectable
Overload
%
100%~110% for 60min
110%~125% for 10min
126%~150% for 1min
>150% for 200ms
Steady state voltage stability %
±1 (balanced load), ±2 (100% unbalanced load)
Total harmonic voltage
%
<2 (linear load), <5(non-linear load)
Synchronization window
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)
Output rated current
(@480V)
70kW
A
70kVA/70kW
84
140kVA/140kW
168
210kVA/210kW
253
280kVA/280kW
337
350kVA/350kW
421
420kVA/420kW
505
490kVA/490kW
589
560kVA/160kW
674
630kVA/630kW
758
700kVA/700kW
842
Output rated current
(@480V)
50kW
module
A
50kVA/50kW
60
100kVA/100kW
120
150kVA/150kW
180
200kVA/200kW
241