UPS Management
UPS command group
The UPS command group allows monitoring and configuration of the managed UPS system.
Command
Parameters
Description
upsinfo
(*)
Show detailed UPS information
attacheddevice
[device]
Set UPS attached device
[device] Device which is powered/protected by the UPS
NOTE
: Maximum length 63 chars. If this parameter contain
blanks or special characters it shall be specified in between
double quotation marks (“...”)
alarmdelay
[time]
Set alarm delay time (1-ph/SP version ONLY)
[time] Time in seconds before alarm notification
NOTE
: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
retrydelay
[time]
Set retry delay time (1-ph/SP version ONLY)
[time] Time in seconds between re-connection attempts
NOTE
: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
retrycount
[count]
Set retry count (1-ph/SP version ONLY)
[count] Number of re-connection attempts
NOTE
: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
serialbypass
on | off
Enable/disable the serialbypass functionality
NOTE
: This command is offered for UPS service access ONLY.
It use outside of this scope is not recommended (enabling
this functionality stops the UPS monitoring
cardaddress
[address]
Show/Set card address on the IMV bus
[address] Card address in the range 0, 54-57
NOTE
: 3-ph version ONLY
This setting may overrides the HW setting through the dip-
switches on the card. Setting this parameter to 0 reverts to
the HW settings.
This setting becomes active only after reboot (save the set-
tings!)
ntp-ups
on | off
Enable/disable the synchronization of the UPS time with an
external reference via NTP protocol.
NOTE
: 3-ph version ONLY
readonlymode
[on | off]
Enable/disable write commands to the UPS
Setting readonlymode to on will stop any write operation to-
wards the UPS (the SNMP/Web adapter will effectively switch
to read-only mode). The UPS Test, Control and Config web
pages will not be shown in the navigator bar.
Caution! Once enabled, this setting may not be reverted.
NOTE
: 1-ph/SP versions ONLY
(*) By running these commands, an interactive menu is launched – follow the on-screen instructions. The menu
also provide a complete on-line help section.