8
Verze 1 – GBR (25.8.2020)
D-502-0171
-
other technical parameters can be found in the catalogue sheet
3.
Installation – installation of air curtains in the working position
3.1.
General information, recommendations and safety during installation of the Wind air curtain
3.1.1.
Electrical safety when installing the curtain
-
Before starting any assembly works, it is necessary to switch off the power supply to the prepared
electrical installation for subsequent activation of the unit. During installation, the switch must be
secured against being switched on again.
3.1.2.
Modification of existing heating distribution systems
-
It is appropriate to use filters for rough impurities in the heating systems to protect the water exchanger
from possible damage from the existing distribution systems.
3.1.3.
Load bearing capacity of the assembly site
-
The selected assembly site must be suitable for the permanent load by the curtain. In case of doubt, the
load capacity of the wall/walls must be verified by a structural engineer or other responsible person.
3.1.4.
Minimum assembly distances
-
The minimum intake distance (fan) of the curtain from the wall/ceiling is 0.3 m.
-
The minimum distance between the side of the curtain and the wall is 0.1 m (assess a suitable distance
from the side of the exchanger outlets to allow easy connection).