The supply cabling for the heater must be a separate supply including the switched phase controlled
by the unit, under no circumstances must the heater be powered from the unit.
-
Sample wiring diagram:
Fig. 37
-
Install the heater - reheater according to the heater manufacturer's instructions e.g.: flow direction,
distance from the unit, heater position, distance of temperature sensor from the heater etc...
-
If the heater manufacturer requires a minimum line velocity for proper heater operation, this must be
addressed by a separate component (e.g.: differential pressure sensor). Under no circumstances shall
the unit be used for this purpose.
-
In no event shall the manufacturer of the unit be liable for improper installation, malfunction or
damage caused by the heater.