Page | 66
-
Series. Automatic Parameter configuration
-
Time. Select Time Zone. Tick Automatically update datalogger with correct time.
-
Set alarm limits.
o
Battery Voltage. Battery Saver (12.75V), Battery Shutdown (12.60V)
o
High Cellular Data. 50000kB
o
Humidity Alert (50%), Humidity Alarm (60%)
o
Temperature (50°C = High internal temperature, may damage lithium batteries, -5°C = Low internal
temperature, may damage lithium batteries)
o
Low Memory (<1000, Low memory, recommend rebooting)
o
Watchdog Error (>0, Watchdog error has occurred, recommend investigating)
27
To setup alarm thresholds for a
parameter, right click on the parameter
from the navigation tree on the left,
select Properties and change to the
States tab. The position relative to the
NORMAL state determines if it is a higher
or lower alarm. The States can be
reordered by dragging the
≡
symbol at
the top right of each State box. To make
a HIGH alarm (i.e., greater-than), have
the State
above
the Normal state. To
make a LOW alarm (i.e., less-than), have
the state
below
the Normal state (as
shown in the image here). Edit the state
to set the name (i.e., Battery Saver),
threshold value (i.e., 12.75V), and the category.
Several alarms (i.e., Battery and Internal Humidity) are configured in the template, while measurement alarms are
specific to the station.
13.2
Setting up LoggerNet
When configuring LoggerNet, follow the steps from page 7 in this manual:
. Refer to the Pakbus Router section for details on the URL. There is no password and remember to set
4070 for the PBRouter in the tree.
13.3
Setting up Hydrosphere
Hydrosphere is the Xylem supported cloud data access platform. Access Hydrosphere here:
https://cloud.xylem.com/hydrosphere
To set up Hydrosphere, two steps are required, first in Hydrosphere and then in the datalogger program.
13.3.1
Hydrosphere Configuration
The Ai1 includes a program that periodically connects to Hydrosphere and sends a buffer of 5 collected data sets (to
backfill historical data during periods of communications outages).
From the dashboard click the
⊕
next to
Create New
and select
Site
.
27
Note that one-off watchdog error may not be a problem unless the error occurs a few times. If several watchdog errors have occurred, file the watchdog diagnostic file (File Control tab) and send to support for
diagnosis.