Page | 26
high precision 24-bit ADC, with 0 to 6V signals, or 4-20mA signals being measured through a configurable resistor
network. Analog inputs are fitted with surge protection.
Intern (JST) Terminal
Connection External (M12) Sensor
Protection
1: Red
SW12 or BAT
→
1: Brown
Sensor Power
1-Stage (TVS)
2: Black
GND
→
4: Black
Ground
Earth lug
3: Yellow
SDI12 (C1 or C2)
X
2: White
Analog In 1
1-Stage (TVS)
4: Green
Not used
3: Blue
Analog In 2
1-Stage (TVS)
5: Blue
Not used
5: Grey
Analog In 3
1-Stage (TVS)
(uses
Digital
main board header)
Voltage to Current (4-20mA)
Converts 0 to 2.5V to 4-20mA output signal.
Intern (JST) Terminal
Connection External (M12) Sensor
Protection
1: Red
BAT
→
1: Brown
Power
1-Stage (TVS)
2: Black
GND
→
4: Black
Ground
Earth lug
3: Yellow
User defined
→
2: White
User defined
1-Stage (TVS)
4: Green
User defined
→
5: Grey
User defined
1-Stage (TVS)
5: Blue
0-2.5V (Vx1)
X
3: Blue
I
out
(4-20mA)
1-Stage (TVS)
(uses
Analog
main board header)
4-20mA Current Output module (Modbus RTU)
Two varieties are available, a 1-channel and 4-channel models, providing independent 4-20mA output signals,
controlled using Modbus RTU commands. (FUTURE)
RS232 to HART (4-20mA) Output module
Provides a HART compatible 4-20mA output signal, controlled using the dataloggers RS232 port. A CRBasic library is
provided for serial communications to the interface. (FUTURE)
RS232 to UART
Converts datalogger RS232 port to TTL UART.
Intern (JST) Terminal
Connection External (M12) Sensor
Protection
1: Red
SW12V
→
1: Brown
Sensor Power
1-Stage (TVS)
2: Black
GND
→
4: Black
Ground
Earth lug
3: Yellow
RS232 RX
X
2: White
UART RX
1-Stage (TVS)
4: Green
RS232 TX
X
5: Grey
UART TX
1-Stage (TVS)
5: Blue
5V (Vx)
→
3: Blue
5V (Vx)
1-Stage (TVS)
(uses
Digital
main board header)
RS232 to RS485
Converts datalogger RS232 port to RS485, with 3-stage surge protection for increased protection .
Intern (JST) Terminal
Connection External (M12) Sensor
Protection
1: Red
BAT/SW12V
→
1: Brown
Sensor Power
3-Stage
2: Black
GND
→
4: Black
Ground
Earth lug
3: Yellow
RS232 RX
X
2: White
Not used
3-Stage
4: Green
RS232 TX
X
5: Grey
RS485_A (-)
3-Stage
5: Blue
5V (Vx)
X
3: Blue
RS485_B (+)
3-Stage
(uses
Digital
main board header)
3-Stage Surge Protection (4-wire)
Provides 3-stage surge protection to incoming wires
Intern (JST) Terminal
Connection External (M12) Sensor
Protection
1: Red
User defined
→
1: Brown
3-Stage
2: Black
GND
→
4: Black
Earth lug
3: Yellow
User defined
→
2: White
3-Stage
4: Green
User defined
→
5: Grey
3-Stage
5: Blue
User defined
→
3: Blue
3-Stage
(uses
Digital
main board header)