PAGE 19
Aquavar IPC Start-Up Genie
Xylem
For Multi-Control configuration here are the
parameters that will get autoset:
Autoset Configuration
Constant
Pressure
Transducer Max Feedback
300 [unit]
Transducer Type
4-20mA
Feedback 1 Source
AI 53
PID Performance
Normal
Sleep Mode
Enabled
Sleep Frequency
30 Hz
Restart Difference
10 [unit]
No Water/Loss of Prime Fault
Enabled
No Water/Loss of Prime Restart Time
Enabled
Duty Standby
Disabled
Stage Speed
95%
Destage Percentage
80%
Alternation Function
On Run Time
Alternation Time
24 Hrs
Pump Exercise
Disabled
Acknowledge Auto Set Settings by pressing
the down arrow and cyclying through each of
the four screens.
For further Multi-Pump Setups, Feedback
Setup, Pump Protection Setup, Flow
Compensation, Pipe Fill Setup, please refer
to the IOM.
Select OK to verify Genie is completed.
3/4
Destage Percentage =
80%, Alternation
Function = On Run Time,
Alternation Time = 24
hrs., Pump Exercise =
[unit], No Water/Loss of
Prime fault is enabled,
Restart Time = 10 mins,
Duty Standby = Disabled,
Stage Speed = 95%,
2/4
Constant pressure with
300 [unit], 4-20mA
sensor on AI 53, Sleep
Frequency = 30Hz,
Restart Difference = 10
1/4
disabled. [OK]
4/4
Start-Up Genie Complete.
Press [OK] to Exit