background image

4

4

8

8.5. Installation notes

•  According to ISO 4064:2013, the Cordonel meter does not require an inlet and outlet section (U0D0).
•  The Cordonel meter does not require an inlet section, not even behind 90° pipe bends.
•  The installation point should be the same length as the meter plus twice the thickness of the flange gaskets used.
•  For outdoor installations Sensus recommends the meter display installed in a shaded location. Direct exposure to sunlight of the meter head 

can increase the inner temperature of the meter, thus drastically reducing the battery life time.

•  Before installation in horizontal lines, align the display in such a way that the numbers can be read easily in the intended main reading posi-

tion. (Avoid overhead positions)

•  According to Directive 2014/32/EU (MID), the meters are classified in mechanical environment class M2 (considerable to strong vibrations 

and shocks).

•  The pipe cross-section must not be reduced or extended abruptly directly upstream or downstream of the meter. All cross-sectional changes 

should be made concentrically at an angle of <8°.

•  All flow regulation components (e.g. valves) must be mounted downstream of the meter in the direction of flow.
•  Flange gaskets must not protrude into the pipe.
•  Flush the pipe thoroughly before installing the meter. 
•  After installation, fill the pipe slowly to prevent damage to the meter caused by water hammers.
•  Select the installation point making sure that air bubbles cannot form in the meter and the pipe is always filled completely. Do not install 

the meter at the highest point of the pipe. It may be necessary to provide suitable de-airing in the direction of flow upstream of the meter.

•  Use suitable measures to protect the meter against water hammers in the pipe.
•  Do not carry out welding work on the pipe with the meter installed to avoid overheating.

8.6. Commissioning

After correct installation and filling, the meter automatically determines its main direction of flow. During the detection period, the two arrows 
above the volume display will flash. The main direction of flow is defined as the direction of flow in which 5 m³ of water first flows after installation. 
The main direction of flow is fixed when only one arrow is permanently visible in the display.
Note that the volumes that flow through the Cordonel while in testing mode are not added together to determine the main direction of flow.

8.7. Operating notes

•  During normal operation, the pipe pressure upstream of the meter must not fall below 0.3 bar in order to avoid cavitation at higher flow rates. 

For flow rates greater than Q

4

, the pressure downstream of the meter must be greater than 1 bar.

•  The pipe should always be filled completely with water during operation.
•  The manufacturer’s specification of the Q

3

 must not be exceeded for a longer period of time.

•  The maximum media temperature should not exceed 50 °C during operation or 70 °C at standstill.
•  Avoid permanent ambient temperatures above 60 °C to enjoy full battery capacity.

 

9. Reading

9.1. Display description

The Cordonel meter has an LC display with two lines. Numbers and symbols are displayed.

1

 

Volume value

2

 

Volume unit 

3

 

Flow rate, pressure or temperature value

4

 

Flow rate, pressure or temperature unit

5

 

Current direction of flow

6

 

Radio activated (flashing)

7

 

Alarm flag

8

 

Low battery level, less than 12 months remaining

Meter in testing mode

10 

Main direction of flow

11

,12  Not used

Cordonel

Page 5

Summary of Contents for Sensus Cordonel DN 100

Page 1: ...Cordonel Static Flow Meter Installation and Operating Instructions...

Page 2: ...Commissioning 5 8 7 Operation notes 5 9 Reading 5 9 1 Display description 5 9 2 Display sequence 6 9 3 Alarms 6 9 4 Testing mode 7 10 Data logger 7 11 Radio 8 11 1 General 8 11 2 SensusRF 8 11 3 wM Bu...

Page 3: ...receive ultrasonic signals with and against the direction of flow of the water The time the signal takes to go from the transmitter to the receiver is measured The flow velocity is calculated using th...

Page 4: ...O 4064 5 2014 The meters are disinfected after the production process Handling during installation must be carried out in accordance with applicable hygiene rules We refer in particular to VDI DVGW Gu...

Page 5: ...iring in the direction of flow upstream of the meter Use suitable measures to protect the meter against water hammers in the pipe Do not carry out welding work on the pipe with the meter installed to...

Page 6: ...rm flag and alarm code Alarm Code Description Comment ALr 001 Low battery alarm Appears when the remaining battery life is approx six months ALr 004 Empty pipe alarm Appears when the measuring pipe is...

Page 7: ...adio command The testing mode is terminated automatically after 72 hours at the latest The time of the automatic termination of the testing mode can be set using the Diavaso config app Switching to te...

Page 8: ...5 seconds After every fourth BUP the meter listens for a short period LAT as to whether further information is requested If a radio com mand PAM is received during this period the meter sends the corr...

Page 9: ...saved meter reading Volume unit Time that data was last saved 13 Factory settings Values Unit DN 40 DN 50 DN 65 DN 80 DN 100 Leakage duration Days 14 Leakage threshold value m h 0 25 0 375 0 625 0 875...

Page 10: ...e Off Key date value net volume On Key date value alarm status On Wake up interval Sec 3 UTC time shift Hours 0 Pulse On Pulse mode A4 balanced pulse Pulse value Litres 100 Pulse length ms 500 1 The i...

Page 11: ...bserve section 8 2 18 Transportation The meters should be transported dry as frost free as possible and under hygienically harmless conditions If possible the meters should always be transported in th...

Page 12: ...ity Cordonel Page 12 Sensus GmbH Hannover Meineckestra e 10 30880 Laatzen T 49 0 5102 74 0 F 49 0 5102 74 3341 Email info int xylem com www sensus com MB 2000 INT Version 0004 May 2021 Subject to chan...

Reviews: