background image

Heat / Cooling Meters Calculator Unit  
PolluTherm can be combined with PolluFlow 
Installation and Operating Instructions 

 

 

MH 6114 INT PolluTherm, Page 5 

new seals. With flanges, make sure that the 
cross-section of the pipe is not reduced by the 
positioning of the seals. 

 
Installation in cooling systems: 

 

It is recommended to install the flow sensor into 

the warm pipe (return) of the cooling system.  

PolluTherm X (installation into the warm pipe) 

must be used in cooling systems. If Sensus flow 

sensors are used, note to the approved 

temperature range. 

 

5.2 Installation of the Temperature Sensor 

 
PolluTherm is operated using a pair of 
temperature sensors, Type Pt 500. The type of 
temperature sensors that can be used is given on 
the front of the calculator unit. 
 

In accordance with the guideline of the PTB 
TR K 9, heat and cooling meters with nominal 
flows of 

 Qp 6m³/h, only direct immersion is 

permitted (refer to MID starter kit) (refer to 
Figure 6) when installing the temperature 
sensor into new installations of the pipeline 
section in the area of the measurement 
position with nominal pressures of 

 16 bar,. 

Here, our MID starter kit should be used. This 
consists of special ball valves with temperature 
sensor seat M10 x 1, with integrated union nuts 
and an adapter (refer to Datasheet MH 1131 DE). 
These starter kits are compatible with the 
temperature sensor types L = 45 mm / 

ø

 = 5.2 

mm and DS 27.5. They are supplied up to 
R1“(DN 25). 
 
The EN 1434-2 can be used as a general 
installation guideline. 
 
When using Sensus temperature sensors with the 
installation lengths of 100 mm and 150 mm, the 
active measuring part is measured approx. 10 to 
15 mm from the tip of the temperature sensor and 
must be located as close as possible to the centre 
in the pipeline. For these types, it is 
recommended to install as follows: 
 
Nominal diameters 

 DN 80*: Installation of the 

temperature sensor at an angle of 45° against the 
direction of flow (refer to Figure 4).  
 
Nominal diameters 

 DN 65*: Installation of the 

temperature sensor vertical to the direction of flow 
(refer to Figure 5). 
 

* For DN 65 and DN 80, both installation positions are 
permitted, up to DN 50, installation is also possible in the pipe 
elbow 

For larger nominal diameters (from approx. DN 
150) the sleeve must be immersed a minimum of 
50 mm into the pipeline. 
 
 
 
 
  
 
 
 
 
 

Figure 4: Exemplary illustration for

 

Nominal diameter DN 50 

 
 
 
 
 
 
 
 
 
 
 

 

Figure 5: Exemplary illustration for 

Nominal diameter DN 100 

 

 

 

Figure 6: temperature sensor, direct 

immersion 

 

5.3 Installation of the Calculator Unit 

 
Use the C-rail with two bolts to attach the 
calculator in the horizontal position at the required 
position. Place the housing on the C-rail and use 
a flat-head screwdriver to raise the red snap-in 
hook. 
Next, press the housing onto the C-rail and 
release the snap-in hook. Alternatively, the 
calculator unit can also be directly installed onto 
the flow sensor. 
 

 

 

 

Messaktiver Teil

 

Tauchhülse

 

Tempera

 

-

 

turfühler

 

ca. 10

 

-

 

15 mm

 

 

 

Messaktiver Teil

Tauchhülse

Temperaturfühler

ca. 10-15 mm

Summary of Contents for SENSUS PolluTherm

Page 1: ...ing Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 1 PolluTherm PolluFlow compatible Installation and Operating In...

Page 2: ...ule for M Bus slot 14 10 6 LONWORKS FTT10A 14 10 7 Inserting the Plug In Modules into the Calculator Unit 14 10 8 Combined Heat Cooling Meter Order Option 14 10 9 Optional Integrated Data Logger Order...

Page 3: ...Discharged batteries electronic devices or components that are no longer required must be disposed of as hazardous waste at suitable collection points If multiple meters are used in a billing unit sim...

Page 4: ...sensor should be installed in the heating flow or the warm pipe The direction of flow is indicated by an arrow on the housing The permitted operating pressure and operating temperature must not be exc...

Page 5: ...7 5 They are supplied up to R1 DN 25 The EN 1434 2 can be used as a general installation guideline When using Sensus temperature sensors with the installation lengths of 100 mm and 150 mm the active m...

Page 6: ...blish strain relief using a cable tie Figure 9 The pulse line white is connected to the terminal 10 and the line GND blue connected to the terminal 11 The terminal 9 is provided for the voltage supply...

Page 7: ...ollowing allocation applies Supply temperature sensor warm pipe Type of connection Terminals Two wire system 5 6 Four wire system 5 6 and 1 2 Pos available shielding Return temperature sensor cooling...

Page 8: ...ive levels can be accessed by pressing the red button for 8 seconds The selection menu appears L1 to L6 User level Due Date level Archive level Service level Control level for tariff purposes Paramete...

Page 9: ...ting 0 Secondary M Bus address Factory setting Serial number 7 2 Due date Level Example All display positions are indicated by an arrow Display of all values are saved to an adjustable due date in the...

Page 10: ...the second external meter Maximum flow in the selected month with date averaged Maximum flow in the selected month with time averaged Maximum energy in the selected month with date averaged Maximum e...

Page 11: ...point for inlet flow temperature cooling metering if activated Switching point for outlet temperature difference cooling metering if activated Correction factor for water frost protection mixture if a...

Page 12: ...n point of the temperature sensors Cover of the calculator unit pull lockwire through the eyelet at the bottom edge 9 Possible Error Situations PolluTherm is equipped with an automatic self monitoring...

Page 13: ...g The primary address can be set at between 0 and 250 and when delivered factory default is set at 0 Battery devices have an M Bus credit as such the daily read out is limited depending on the number...

Page 14: ...omatic switching point The factory setting for switching to cooling metering is Flow temperature 25 C and Negative temperature differential 0 15 K To switch back to warm metering the following applies...

Page 15: ...able for the temperature sensors can be extended to a maximum of approx 23 m In order to compensate for the additional cable resistance the so called four wire system is used Cable with four wires is...

Page 16: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instruction MH 6114 INT PolluTherm Page 16...

Page 17: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 17...

Page 18: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instruction MH 6114 INT PolluTherm Page 18...

Page 19: ...Heat Cooling Meters Calculator Unit PolluTherm can be combined with PolluFlow Installation and Operating Instructions MH 6114 INT PolluTherm Page 19...

Page 20: ...tallation and Operating Instruction MH 6114 INT PolluTherm Page 20 Material number 28505234 Version 10 2021 0007 subject to modifications Sensus GmbH Ludwigshafen Industriestra e 16 D 67063 Ludwigshaf...

Reviews: