Manual Ozone Generating System SMOevo
Safety
Rev. 1.0
Page 21 of 91
Do not enter the operating room until the ozone concentration has fallen below the
alarm limit value.
Preferably use CO
2
fire extinguishers in case of fire.
Never extinguish fire in or at the electrical cabinet with water.
Immediately inform a physician or emergency service and provide first aid if a person
has been injured.
Notify your superior of all accidents.
3.6 Requirements for the Installation Place
Location
Ensure that the ozone system is installed in a closed, frost-free,
lockable room.
Ensure that the ozone system is protected from direct sunlight.
The installation foundation must be designed for the operating
weight of the ozone system.
Refer to
section Dimensions and Weights.
The installation surface must be dimensioned in such way that
operation, maintenance, and repair can be easily carried out.
Sufficient space for air circulation around the ozone system must be
included.
Refer to section Operating Room.
Do not allow permanent workplaces or work stations in rooms
housing ozone systems. If the installation site of the system cannot
be separated from the workplace for technical processing reasons,
reliably monitor the ozone concentration in the ambient air. Ensure
the maximum allowable threshold limit value of
0.2 mg/m
3
(
≈
0.1 ppm
v
) is not exceeded.
Technical
Ventilation
Ensure that rooms housing ozone systems are equipped with a
technical ventilation system guaranteeing an air exchange of at
least three times per hour. An extraction type ventilation must exist
with the intake opening located directly above the floor. The
ventilation system must turn on automatically when a gas detector
responds to the potential danger.
Special Safety
The installation place of the ozone system must be in accordance
with the locally applicable occupational health and safety
regulations. In particular, observe the regulations with regard to
room ventilation, accessibility, and escape routes.
Ensure that rooms are effectively monitored regarding room
ventilation by means of gas detectors with visual and acoustic
indicators which interrupt the ozone production immediately once
being activated.
The air filter in the breathing mask lasts for approx. 10 minutes