Manual Ozone Generating System SMOevo
Error! Use the Home tab to apply Überschrift 1 to
the text that you want to appear here.
Rev. 1.0
Page 46 of 91
5.3.3 Subassembly 03: Process Gas Line
BV310-2
03.0.10
Ball valve
Isolation valve for PI310-1
PI310-1
03.0.15
Pressure
gauge
To read the operating pressure of the ozone generator.
Refer to the setpoints in section Operating Data.
FCV310
03.0.20
Motor control
valve with
actuator
To set the gas volume flow of the ozone system via touch
panel.
Refer to section Operation
.
In case of fault or outage the
valve closes automatically.
CV310
03.0.20
Check valve
To secure the system against flow in opposite direction.
BV310-4
03.0.25
Ball valve
Open in normal operation. To be closed manually only in case
of shutting down the system for a longer period of time, e. g.
for maintenance purposes.
Option: Ozone Monitor
SV310-2
03.0.01
Solenoid
valve
The branch for connection of the optional ozone monitor (M1,
M2, or M3) is located downstream the ozone generator. An
ozone monitor can calculate the produced ozone mass in a
precise way.
Refer to section Control Modes.
Optionally an automatic control for calculation of the required
ozone mass can be included, e. g. in connection with an
external setpoint device.