background image

System 182-XT-4

Relay outputs

6 - 17

ba76027e02

12/2014

6.4.4

Limit indicator

Function

The characteristic of the limit indicator is laid down in the Limit value 
UL
Limit value LLHysteresis UL and Hysteresis LL settings. The 
fundamentals of the function are described in the introductory chapter 
(see section 6.3.2).

In order to set up the Limit indicator function for a relay output, the relay 
output must be linked with a sensor (see section 6.2.1).

Settings

Setting

Selection/Values

Explanation

Limit values

UL main variable
LL main variable

UL adjoining var.
LL adjoining var.

Main variable 
designates the actual 
measured parameter 
of the sensor (e.g. pH, 
oxygen, etc.).
Adjoining variable 
designates an 
additional measured 
parameter (e.g. 
temperature).

Limit value UL

Within the measuring 
range (sensor-
dependent)

Any upper or lower 
limiting value

Limit value LL

Hysteresis UL

0 - 10 % of the 
measuring range

Hysteresis for upper or 
lower limiting value

Hysteresis LL

Behavior at error

Open
Close
Unchanged

The relay opens, 
closes or remains 
unchanged in the case 
of system errors or 
sensor errors (see 
page 6-25).

Action

Open
Close

Relay action

Switching delay

0 ... 3600 s

The time period for 
which a limiting value 
must be exceeded 
before the relay 
operates.
Prevents frequent 
switching for 
measured values that 
are close to the limiting 
value.

Summary of Contents for YSI 182-XT-4

Page 1: ...OPERATIONS MANUAL ba76027e02 12 2014 DIQ S 182 XT 4 PR System 182 XT 4 MODULAR MEASURING SYSTEM FOR 4 DIGITAL SENSORS WITH PROFIBUS DP INTERFACE...

Page 2: ...4 For the most recent version of the manual please visit www ysi com Contact YSI 1725 Brannum Lane Yellow Springs OH 45387 USA Tel 1 937 767 7241 800 765 4974 Email environmental ysi com Internet www...

Page 3: ...power rating 3 3 3 1 5 Optimum installation of the additional MIQ power supply module 3 5 3 2 Safety requirements on the electrical installation 3 6 3 3 Installation guidelines for lightning protecti...

Page 4: ...status display 4 2 4 3 Working with the SETTINGS menu 4 4 4 3 1 Selection menus 4 4 4 3 2 Setting tables 4 5 4 3 3 Entry mode 4 6 4 4 PROPERTIES menu 4 8 4 4 1 Overview 4 8 4 4 2 Maintenance condition...

Page 5: ...7 Maintenance and cleaning 7 1 7 1 Maintenance 7 1 7 2 Cleaning 7 1 8 What to do if 8 1 8 1 Information on errors 8 1 8 2 Error causes and remedies 8 1 8 3 Replacing system components 8 2 8 3 1 Replac...

Page 6: ...Contents System 182 XT 4 0 4 ba76027e02 12 2014...

Page 7: ...cording to the number of available main measured variables individual sensors one physical sensor for each main measured variable and multiple sensors one physical sensor for several main measured var...

Page 8: ...anual IQ SENSORNET Field bus linking Cleaning system driven by compressed air The DIQ S 182 XT 4 PR is prepared for the time controlled sensor cleaning function driven by compressed air The cleaning p...

Page 9: ...ollowing settings Sensor settings Settings and links of the relay outputs PROFIBUS settings System settings display language air pressure altitude passwords etc Linked relay outputs switch to the non...

Page 10: ...Overview System 182 XT 4 1 4 ba76027e02 12 2014...

Page 11: ...can lead to serious irreversible injury or death if the safety instruction is not followed CAUTION indicates a possibly dangerous situation that can lead to slight reversible injury if the safety ins...

Page 12: ...y sources mentioned in this operating manual The product may only be operated under the environmental conditions mentioned in this operating manual The product may not be opened 2 2 3 Unauthorized use...

Page 13: ...ual of the relay output module WARNING A circuit except for the power supply connections that is connected to an DIQ S 182 XT 4 PR component must not feed any voltages or currents that are not allowed...

Page 14: ...Safety System 182 XT 4 2 4 ba76027e02 12 2014...

Page 15: ...ry of the DIQ S 182 XT 4 PR DIQ S 182 XT 4 PR with attached MIQ JB branching module Accessory kit with Contact carrier with screws ISO cap nuts with screws and ring washers Cable glands with sealing g...

Page 16: ...take into account the relative switching on time of valves Number and types of required sensors Measuring locations to be designed Distances Infrastructure process environment etc Rough planning Deter...

Page 17: ...require a specific level of electrical power for operation Thus it is necessary to draw up a power rating after selecting the desired components At the same time a determination is made of whether th...

Page 18: ...relative on time P Pnominal ED Since ED is always 1 the effective power requirement is always smaller than the nominal power of the valve component Determining the number of MIQ power supply modules F...

Page 19: ...the MIQ Blue PS 3 1 5 Optimum installation of the additional MIQ power supply module Basic rule It is preferable to install the MIQ power supply module in the vicinity of the IQ SENSORNET component w...

Page 20: ...ce input or output Overvoltage class II surge limiters Suitable disconnecting device e g switch or circuit breaker for the mains supply of permanently mounted equipment with separate mains connection...

Page 21: ...h overvoltages developing along the line at the same time that could have a damaging effect on the individual IQ SENSORNET components It is not recommended to use cables from other manufacturers with...

Page 22: ...ng protection measures directly on the IQ SENSORNET system or its components e g the use of overvoltage surge arresters are not necessary for protection against the indirect effects of lightning and c...

Page 23: ...s The DIQ S 182 XT 4 PR or an MIQ module is attached by its back to the lid of an MIQ module from page 3 10 Select this variant if an MIQ module is already permanently installed e g to a wall Variant...

Page 24: ...tion variants of the attachment of an MIQ module on the DIQ S 182 XT 4 is described in the following The assembly of further MIQ modules is carried out analogously To dismantle a stack proceed in the...

Page 25: ...e the contact cover pos 2 3 Pull off the adhesive label pos 4 Only use the plastic tapping screws supplied for attaching the contact base They ensure the correct fit 4 Fix the contact base pos 5 in Fi...

Page 26: ...SO blind nuts variant 1 Stacking the MIQ modules Fig 3 5 Stacking the MIQ modules variant 1 6 Insert the cheese head screws pos 8 in Fig 3 4 with the plastic washers in the drilled mounting holes in t...

Page 27: ...S 182 XT 4 PR to the cover of the MIQ module At the same time ensure that the two clips on the DIQ S 182 XT 4 PR click into place in the lid of the MIQ module Subsequently tighten the two screws pos 8...

Page 28: ...2 Remove the contact cover pos 2 3 Pull off the adhesive label pos 4 4 On the MIQ module remove the two countersunk screws pos 5 and swing open the module lid Only use the plastic tapping screws suppl...

Page 29: ...ISO blind nuts variant 2 Stacking the MIQ modules Fig 3 10 Stacking the MIQ modules variant 2 6 Insert the cheese head screws pos 8 in Fig 3 9 with the plastic washers in the drilled mounting holes i...

Page 30: ...T connections The DIQ S 182 XT 4 PR has a SENSORNET connection on the front terminal strip and four others on the rear terminal strip The terminal strips are shown in section 3 12 In addition free SEN...

Page 31: ...of all MIQ modules in the System 182 must be set to Off Materials required 1 x SNCIQ or SNCIQ UG connection cable see chapter 11 ACCESSORIES AND OPTIONS Wire end sleeves for 0 75 mm2 wire cross secti...

Page 32: ...to the terminal strip in the same way as the SACIQ sensor connection cable see section 3 4 5 SNCIQ SNCIQ UG approx 35 mm approx 45 mm approx 45 mm 1 Open the enclosure of the DIQ S 182 XT 4 PR or the...

Page 33: ...pling ring pos 3 in Fig 3 13 5 Feed the cable through the cable gland into the enclosure 6 Connect the cable ends to the terminal strip At the same time look out for the designations of the terminals...

Page 34: ...cable gland matched to the cable diameter see section 3 7 on page 3 31 The free end of the connection cable already has the sheath removed in the factory and all the wires are fitted with wire end sle...

Page 35: ...SACIQ cable with the IQ sensor 3 Then screw the coupling ring 2 of the IQ sensor connection cable on the IQ sensor up to the stop For further instructions on the mounting of IQ sensors at the applicat...

Page 36: ...tion for theDIQ S 182 XT 4 PR are described in the following chapters Mounting on a mounting stand with the SSH IQ sun shield The SSH IQ sun shield provides enough space for the DIQ S 182 XT 4 PR and...

Page 37: ...un shield see chapter 11 ACCESSORIES AND OPTIONS Tools 4 mm set screw wrench Phillips screwdriver Mounting the sun shield on a mounting stand Fig 3 15 Mounting the SSH IQ sun shield on a mounting stan...

Page 38: ...ting the DIQ S 182 XT 4 PR on the sun shield Fig 3 17 Mounting DIQ S 182 XT 4 PR on the protective cover of the SSH IQ 2 Remove the two countersunk screws pos 5 in Fig 3 16 and swing open the lid 3 In...

Page 39: ...ecess behind the Universal Transmitter to the top of the housing Fig 3 18 DIQ S 182 XT 4 PR with PROFIBUS cable at the sun shield 4 Position the DIQ S 182 XT 4 PR on the sun shield and fix it into pla...

Page 40: ...el aperture Fig 3 19 Mounting aperture in the switch panel dimensions in mm Mounting the DIQ S 182 XT 4 PR in a switch panel The space required on the panel for DIQ S 182 XT 4 PR is given in the dimen...

Page 41: ...20 but do not remove them 4 Push in the two angle brackets as shown in Fig 3 20 into the lateral guides of the Universal Transmitter up to the stop 5 Tighten the screws pos 2 6 Screw in the screws po...

Page 42: ...1 Screw the clamping assembly item 1 in Fig 3 21 with the two plastic self tapping screws item 2 onto the back of the DIQ S 182 XT 4 PR 2 Attach the DIQ S 182 XT 4 PR onto the top hat rail from above...

Page 43: ...to the DIQ S 182 XT 4 PR Fig 3 22 DIQ JB open The DIQ JB module has seven potential free terminals To extend or branch lines connect the three IQ SENSORNET wires to each other one to one at any termin...

Page 44: ...t and can be mounted directly on a wall For mounting on a YSI mounting stand YSI provides the MS DIQ mounting set It contains a pipe clip for the mounting stand and provides enough space for two DIQ m...

Page 45: ...e cable diameter Small clamping range 4 5 to 10 mm This cable gland is suitable for all IQ SENSORNET cables including earth cable after stripping the outer insulation see section 3 4 4 and IQ SENSORNE...

Page 46: ...ut off any wires that are not in use as closely as possible to the cable gland 3 8 Connecting the voltage supply 3 8 1 DIQ S 182 XT 4 PR line power version WARNING If the power supply is incorrectly c...

Page 47: ...cable gland matched to the cable diameter see section 3 7 on page 3 31 Tools Cable stripping knife Wire stripper Phillips screwdriver Small screwdriver Preparing the power cable Fig 3 25 Prepared pow...

Page 48: ...e of the DIQ S 182 XT 4 PR front terminal strip 6 Screw a cable gland pos 1 in Fig 3 26 with sealing ring pos 2 into the enclosure below the power supply connection 7 Loosen the coupling ring pos 3 8...

Page 49: ...s cut off any wires that are not in use as closely as possible to the cable gland The complete assignment of the terminal strip is shown in section 3 12 9 Connect phases L and N to the terminal strip...

Page 50: ...tion as an interrupt facility for the DIQ S 182 XT 4 PR The interrupt facility must be installed in the vicinity of the DIQ S 182 XT 4 PR easily accessible by the user and marked as an interrupt facil...

Page 51: ...e 4 Open the enclosure of the DIQ S 182 XT 4 PR front terminal strip 5 Screw a cable gland pos 1 in Fig 3 29 with sealing ring pos 2 into the enclosure below the 24 V AC DC connection 6 Loosen the cou...

Page 52: ...wires that are not in use as closely as possible to the cable gland The complete assignment of the terminal strip is shown in section 3 12 8 Connect wires 1 and 2 to the terminal strip Make sure that...

Page 53: ...ot subject to this danger e g the DIQ CHV module may be operated on the further relays Switching voltages and switching currents on the relay contacts must not exceed the values specified in chapter 9...

Page 54: ...hock when working with the System 182 XT 4 Always cut off any wires that are not in use as closely as possible to the cable gland 11 Open the enclosure of the DIQ S 182 XT 4 PR 12 Screw a cable gland...

Page 55: ...nnection in the DIQ CHV in series Bridge a terminal of the auxiliary voltage output with a terminal of a relay output and run a control line from the remaining terminals to the valve module NOTE The a...

Page 56: ...System 182 XT 4 3 42 ba76027e02 12 2014 Installation examples with one and two sensors with compressed air cleaning can be found in section 3 11 Relay connection Auxiliary voltage Bridge Valve control...

Page 57: ...viding measured values Init appears temporarily Fig 3 32 Display during the start phase Start checklist 1 Are all system components correctly connected with one another see section 3 4 2 Are the DIQ S...

Page 58: ...ontrol Example Relay 1 controls the cleaning of sensor 1 Relay 2 controls the cleaning of sensor 2 Variant Relay 1 controls the cleaning of both sensors Cleaning of both DIQ CHV 1 SACIQ SACIQ DIQ CHV...

Page 59: ...ger that areas safe to contact could come into contact with dangerous voltages Always cut off any wires that are not in use as closely as possible to the cable gland X13 X15 X12 X14 X11 X10 X9 X2 X2 X...

Page 60: ...m 182 XT 4 3 46 ba76027e02 12 2014 Connection scheme of the DIQ JB X1 X4 X2 X5 X3 X6 X7 Terminal strip DIQ JB SNCIQ UG SACIQ SACIQ Sensor 2 Sensor 1 green Shield Filler stranded wire black black green...

Page 61: ...2014 3 11 2 Connection of a sensor that is located at a distance without compressed air cleaning 1 1 2 2 3 3 4 4 5 5 6 6 7 7 SNCIQ UG SNCIQ UG SACIQ Sensor SACIQ DIQ JB M C S ESC OK DIQ S 182 XT 4 PR...

Page 62: ...Installation System 182 XT 4 3 48 ba76027e02 12 2014 Connection scheme of the DIQ JB X1 X4 X2 X5 X3 X6 X7 Terminal strip DIQ JB SNCIQ UG green Shield Filler stranded wire black green red red SACIQ...

Page 63: ...3 R2 R1 L1 N 240V AC 2A AC 240V AC 2A AC 240V AC 2A AC AUXILIARY VOLTAGE SENSORNET 1 RED SHIELD GREEN X3 X2 X17 X9 X15 X13 X11 X1 X16 X8 X14 X12 X10 24V AC DC INPUT POWER AUXILIARY R3 R2 R1 240V AC 2A...

Page 64: ...Installation System 182 XT 4 3 50 ba76027e02 12 2014...

Page 65: ...ating situations c Starts calibration of the sensor selected in the measured value display s Opens the SETTINGS menu in the measured value and status display e Switches to the higher menu level Cancel...

Page 66: ...cond intervals Select a sensor in the double display with w The selected sensor is displayed in reverse video The number and name of the selected sensor are displayed in the header In the single displ...

Page 67: ...occurred Error messages from the sensors are entered in the log book The log book is described in detail in section 4 4 3 Error conditions of the system can for example be an insufficient operational...

Page 68: ...etailed information on password protection see section 4 6 The arrows 8 2 appear automatically if further display contents are above or below the visible display range The toggle switch w is used to h...

Page 69: ...gle switch w is used to highlight a setting displayed in reverse video and move the visible display range up or down To edit a setting highlight it and press g The line below is highlighted and switch...

Page 70: ...made character after character Select the first character with the toggle switch w and press g The entry mark moves to the next position and indicates P Select the next character with the toggle swit...

Page 71: ...ng or is only allowed where it makes sense e g at the first position only Save and quit On principle all settings made in the entry mode are only taken over after selecting the Save and quit item in t...

Page 72: ...status Sxx Here you can prompt the following data of a sensor see section 4 4 3 Type series number and software version Data of the last calibration Error and info messages System status Here you can...

Page 73: ...t prompt changes in the conditions of linked outputs The following diagram gives you an overview of when an IQ sensor is in the maintenance condition Maintenance condition ON g m e m c e m g c g Measu...

Page 74: ...tion 4 5 during a compressed air cleaning cycle After the cleaning cycle is finished the maintenance condition is automatically switched off again 1 Switch on the maintenance condition for the IQ sens...

Page 75: ...ay flashes If there are info and error messages present at the same time the error symbol h flashes more important The flashing of the info or error symbol only stops after all detailed message texts...

Page 76: ...book message in the log book consists of one line The latest message is on the first position They are not yet marked with a tick i e acknowledged figure 4 9 Log book 1 Message type error or info symb...

Page 77: ...knowledge messages and view detailed messages Pos Information Explanation 1 Category Info message I Error message E 2 Type Calibration C Installation and commissioning I Instructions for service and r...

Page 78: ...and press g The detailed message text is displayed Scroll through the text with the toggle switch w 5 Press g Thus you acknowledge the message 6 Press g once again This returns you to the log book wh...

Page 79: ...e g key is pressed Return to the measured value display without switching on the maintenance condition with m or e By activating the maintenance condition linked outputs remain in their present state...

Page 80: ...easured value display the measured value flashes as the sensor is still in the maintenance condition 7 If calibration was successful immerse the sensor in the test sample 8 Wait for a stable measured...

Page 81: ...ed Calibration password protects against unauthorized calibration If this password is active the password query appears on calling up calibration with c If no valid password is entered calibration is...

Page 82: ...Operation System 182 XT 4 4 18 ba76027e02 12 2014...

Page 83: ...he following paragraphs 5 2 Language In this menu you can set the system language Procedure Selecting the language To view these menu items scroll down with w 1 Open the SETTINGS menu with s 2 Select...

Page 84: ...all displays of this sensor appear in the standard language English To activate the selected system language for this component a software update of the component is required Contact YSI General steps...

Page 85: ...deleted by this action Procedure Deleting inactive datasets 5 4 Relay output R1 R2 R3 In these menus you can link sensors with the relay outputs of the Universal Transmitter and adjust the outputs Th...

Page 86: ...ssword for the settings For details on the passwords refer to section 4 6 Calibrate a z Here you can configure the password for calibration For details on the passwords refer to section 4 6 Display co...

Page 87: ...ngs Sensor dependent see settings tables in the respective sensor operating manual Note Calibration of the sensor is stored in the sensor and is retained when the system configuration is reset Relay o...

Page 88: ...The SETTINGS menu System 182 XT 4 5 6 ba76027e02 12 2014...

Page 89: ...ing Manual control Relay outputs can be configured as openers or closers Valve outputs MIQ CHV PLUS The MIQ CHV PLUS valve module is administrated by the system as a valve output designation MIQ CHV P...

Page 90: ...o use the output for system monitoring details see section 6 4 2 Procedure linking outputs Proceed as follows if the output was not yet linked If you want to change a link you have to erase the existi...

Page 91: ...red it can be erased Procedure Erasing a link 1 Open the SETTINGS menu with s 2 Using w and g select and confirm the Relay output Rx menu item corresponding to sensor 1 2 or 3 3 Using w select Delete...

Page 92: ...Rx menu item corresponding to sensor 1 2 or 3 3 Confirm the selection Set output with g The setting table of the output is displayed 4 Edit the setting table as described in section 4 3 2 To accept al...

Page 93: ...sed in the following way Monitoring a limiting value using a relay when a limiting value upper or lower limiting value is exceeded or undercut a relay switches The Open or Close relay actions are poss...

Page 94: ...d values are close to the limiting value 1 Upper limit value relay 1 exceeded 2 Selected switching delay t1 for relay 1 expired Relay 1 switches 3 Hysteresis for upper limiting value relay 1 undercut...

Page 95: ...value pulse width output see page 6 9 or switching frequency frequency output see page 6 10 Proportional outputs can be used in the following way Output with one relay An output range is defined with...

Page 96: ...00 Proportional band Measured value 1 2 90 0 Switching frequency f or Pulse v width 1 Start value Measured value with a minimum pulse width or switching frequency 2 End value Measured value with a max...

Page 97: ...emains constant the turn on duration ton changes depending on the measured value and with it the pulse width v The pulse width can be set from 0 to 100 v ton T 100 v pulse width T cycle duration ton t...

Page 98: ...ue in the proportional range the relay is switched more often or less often Fig 6 5 Relay output of frequency output While the selected switching duration ton 0 3 s always remains constant the switchi...

Page 99: ...characteristic curve Select the End value to be smaller than the Start value The turn on duration or frequency decreases with an increasing measured value see page 6 13 The maximum values for the pul...

Page 100: ...g 6 9 Frequency output 1 Start value Measured value with a minimum pulse width or switching frequency 2 End value Measured value with a maximum pulse width or switching frequency 0 10 50 90 100 Propor...

Page 101: ...d behavior comes into force Fig 6 10 Pulse width output Fig 6 11 Frequency output 1 Start value Measured value with a minimum pulse width or switching frequency 2 End value Measured value with a maxim...

Page 102: ...e is displayed Relay function and relevant setting tables Function Setting table No function The relay output is not used System monitoring See section 6 4 2 Sensor monitoring See section 6 4 3 Limit...

Page 103: ...supply a valid secondary measured value In any case the relay remains open for 10 seconds and only closes when the malfunction is no longer present In the following cases the relay does not open desp...

Page 104: ...sensor errors Setting Selection Explanation Errors All All sensor errors special ones and general ones are monitored and can prompt a relay action Special Special sensor errors are monitored and can...

Page 105: ...joining var Main variable designates the actual measured parameter of the sensor e g pH oxygen etc Adjoining variable designates an additional measured parameter e g temperature Limit value UL Within...

Page 106: ...tive characteristic curve In order to obtain a negative characteristic curve a value for End value must be entered that is smaller than the value for Start value Setting Selection Values Explanation M...

Page 107: ...etermines the steepness of the characteristic curve of the output Setting Selection Values Explanation Measured variable Main variable Adjoining variable Main variable designates the actual measured p...

Page 108: ...leaning cycle e g UV VIS sensor Settings Setting Selection Values Explanation Pulse length Automatic The duration of the air cleaning process is programmed in the sensor The relay automati cally takes...

Page 109: ...are frozen The maintenance condition is active After the Cleaning duration the relay is opened During the following Adjustment time the outputs remain blocked The outputs linked with this sensor are o...

Page 110: ...g interval 1 2 3 4 5 6 7 d or 1 2 3 4 6 8 12 24 h or 5 10 15 20 30 60 min Repeat interval for the cleaning function Time between the start time of a cleaning cycle and the start time of the next clean...

Page 111: ...of a cleaning cycle t1 Start of the specified Cleaning duration t1a 2 End of the specified Cleaning duration t1a Start of the specified Adjustment time t1b 3 End of the specified Adjustment time t1b...

Page 112: ...e set up 6 4 9 Manual control Function The Manual control function can be used to test the operativeness of an instrument that is connected to the relay To do so close or open the relay manually and w...

Page 113: ...is non operative when no function is activated for the output The relay contact is open in the non operative condition An output becomes non operative in case of Power failure As soon as the supply vo...

Page 114: ...Relay outputs System 182 XT 4 6 26 ba76027e02 12 2014...

Page 115: ...mpressed air is available on site blow off the worst of the dirt beforehand Keep the enclosure closed while doing so NOTE The enclosure and the window of the display are made of plastic Therefore avoi...

Page 116: ...Maintenance and cleaning System 182 XT 4 7 2 ba76027e02 12 2014...

Page 117: ...ook is described in detail in section 4 4 3 Sensor status SXX 8 2 Error causes and remedies The system does no longer react on entries Error in the measured value display Information on possible error...

Page 118: ...to life due to possible hazard of electric shock Before opening the Universal Transmitter switch off the system and if necessary all external relay circuits that present a hazard of electric shock an...

Page 119: ...cases are possible The DIQ S 182 XT 4 PR can display and administrate up to four main measured parameters If necessary an inactive dataset has to be erased to be able to add a new sensor To erase inac...

Page 120: ...sets Example Replacing an IQ sensor Make sure that the substitute sensor has at least the software status of the inactive IQ sensor be included as a new module in the list of the sensors The operating...

Page 121: ...ensor was selected the system changes directly to the measured value display As soon as the IQ sensor is ready for operation it delivers a measured value If Substitute sensor was selected a list with...

Page 122: ...What to do if System 182 XT 4 8 6 ba76027e02 12 2014...

Page 123: ...ical data 9 1 DIQ S 182 XT 4 PR Dimensions Fig 9 1 Dimension drawing of the DIQ S 182 XT 4 PR dimensions in mm Test marks Side view 143 0 144 0 43 0 11 0 16 5 Front view Rear view 48 48 Stack mounting...

Page 124: ...for conduit connection Temperature Operation 20 C 55 C 4 131 F Storage 25 C 65 C 13 149 F Relative humidity Yearly average 90 Dew formation Possible Site altitude Max 2000 m above sea level Power sup...

Page 125: ...se rating on the operator side max 16 A Power consumption max approx 12 W SENSORNET 1 SENSORNET 2 RED RED SHIELD SHIELD GREEN GREEN X3 X6 X2 X5 X17 X9 X15 X13 X11 X1 X4 X16 X8 X14 X12 X10 100 240V AC...

Page 126: ...t terminal strip 2 A AC and DC Rear terminal strip 5 A AC and DC Fuse rating on the operator side Front terminal strip max 2 A Rear terminal strip Maximum 5 A Relay functions Programmable as Opener or...

Page 127: ...ces for industrial areas intended for indispensable operation Interference emission limits for resources of class B System lightning protection Extended protective characteristics as opposed to EN 613...

Page 128: ...modules Dimensions Fig 9 2 Dimension drawing of MIQ module dimensions in mm Technical data on special MIQ modules are given in the respective operating manuals 100 148 144 0 115 0 70 0 144 0 45 0 72 0...

Page 129: ...fiber Weight Approx 0 5 kg type dependent Type of protection IP 66 In accordance with NEMA 4X MIQ modules are not suitable for conduit connection SENSORNET connections At least two in each MIQ module...

Page 130: ...JB Enclosure material Polystyrene Weight Approx 0 2 kg Type of protection IP 66 1 1 2 2 3 3 4 4 5 5 6 6 7 7 7 passive potential free terminals for line extension or branching Terminal type Screw type...

Page 131: ...rminals to connect interface lines Terminal strip inside the enclosure Terminals 94 94 28 57 DIQ CHV Enclosure material Polystyrene Weight Approx 0 3 kg Type of protection IP 66 VALVE AUXILIARY X2 X6...

Page 132: ...only be operated with the auxiliary voltage of the DIQ S 182 XT 4 PR Compressed air Switching voltage Approx 22 V Max switching current Approx 40 mA Required air quality Dry free of dust and oil Oper...

Page 133: ...hat rail mounting Fig 9 5 Space required for wall and top hat rail mounting dimensions in mm Panel mounting Fig 9 6 Space required for panel mounting dimensions in mm 285 48 200 245 Wall mounting or...

Page 134: ...Technical data System 182 XT 4 9 12 ba76027e02 12 2014...

Page 135: ...System 182 XT 4 1 ba76027e02 12 2014...

Page 136: ...ning a product for service include the Product Return form with cleaning certification The form must be completely filled out for an YSI Service Center to accept the instrument for service The Product...

Page 137: ...Y 480 045Y 480 066Y 480 060Y 480 067Y 480 062Y 480 064VY Set with four cable glands for cable sheath diameter of 7 to 13 mm EW 1 480 051Y Branching module DIQ JB 472 005Y Valve module DIQ CHV 472 007Y...

Page 138: ...Accessories and options System 182 XT 4 11 2 ba76027e02 12 2014...

Page 139: ...5 erasing a link 6 3 Error symbol 4 3 4 11 F Frequency output relay 6 18 I Inactive dataset 5 3 8 3 Info symbol 4 3 4 11 K Key functions 4 1 L Language 5 1 Setting 5 1 System language 5 1 Lightning pr...

Page 140: ...ponents 8 2 S Sensor conditions special ones 4 3 Sensor connection cable SACIQ 3 20 Sensor monitoring relay 6 16 Sensor status 4 11 Sensor controlled cleaning 6 20 SENSORNET connection terminal strip...

Page 141: ...fault passwords In the default condition of the DIQ S 182 XT 4 PR both passwords are set to 1000 1 Open the SETTINGS menu with s 2 Depending on the password to be prompted use w and g to select and co...

Page 142: ...Appendix store separately if required System 182 XT 4 13 2 ba76027e02 12 2014...

Page 143: ......

Page 144: ...and return water to the environment and we help people use water efficiently in their homes buildings factories and farms In more than 150 countries we have strong long standing relationships with cus...

Reviews: