Factory setting: OFF
Different devices in engine and NMEA 2000 networks can have matching addresses. And forwarding
of such messages can cause conflicts. To avoid conflicts, YDEG can use its own, original address
or a specified address as the sender address in the forwarded messages. This is managed by
the PASS_ADDR setting.
OFF value turns off the forwarding of messages, with AS_IS messages being forwarded as is (with original
sender address). If the YDEG value is chosen, the address of Gateway will be used, or you can set a fixed
address in a range of 0 – 253.
The YDEG value is a recommended option in the case of forwarding NMEA 2000 messages.
The AS_IS option should be used to forward J1939 messages. For example, to forward active diagnostic
trouble codes from one or multiple engines:
PASS_PGN=65226
PASS_ADDR=AS_IS
29. SETTING GROUP STARTING WITH J1708
These settings were available in firmware versions up to 1.22 and designed for our experimental
J1708/J1587 adaptor. If you have this adapter, contact us for the latest firmware and manual. Please use
J1708 Engine Gateway YDES-04 for Volvo Penta engines equipped with EDC I and EDC II (KAD, TAMD)
and engines with a J1708/J1587 interface.
30. TRANMISSION_ALERT_MASK=x
x — 5-bit mask, hexadecimal number 00…1F
Factory setting: 1F
Only bits set in this mask can be set by the Device in the transmission status in NMEA 2000. Use of this
parameter is described in Section
VI.6.