Keypad Programming Commands 

General Format 

MC# 

PCC      VALUE 

 

Audible Keypad Feedback 0=DISABLE, 1=ENABLE (Default =1) 

MC# 

31# 

VAL # 

   

  

Visual Keypad Feedback 0=DISABLE, 1=ENABLE (Default =1) 

MC# 

32# 

VAL # 

   

  

Keypad Attempts (1 thru 255) Default = 3 Attempts 

MC# 

33# 

VAL # 

   

  

Keypad Timeout (1 thru 255 Sec) Default = 10 Sec 

MC# 

34# 

VAL # 

   

  

Unlock Time (1 to 255 Sec) Default = 4 Sec 

MC# 

44# 

VAL # 

   

  

Set REX Unlock (1 to 255 Sec) Default = 10 Sec 

MC# 

45# 

VAL # 

   

  

Set Emergency Unlock Time (1 to 255 Sec) Default = 10 Sec 

MC# 

46# 

VAL # 

 
 
Features and Options: 
 

1)  Error  Lockout:

  The  lock  will  stop  accepting  key  presses  after  25  presses  or  three 

successive 

*

 

]

   entries without a valid code. Upon  the third incorrect entry, the lock will 

short  beep  three  times  with  one  short  red  flash  (indicating  invalid  code  entry)  and 
continue to short beep once per second for the duration of the lockout time (no LED will 
light). The lock will not accept any key presses during that 10 second (default) time.  The 
error lockout option overrides the horn disable function (PCC#31). 

 

2)  Low  Battery  Indicator:

   When  the  battery  voltage  drops  below  (5.8  volts)  the  lock  will 

short beep 4 times and allow entry.  If the battery voltage drops below 5.4 volts (Blackout 
Mode), 4 short beeps followed by 4 long tones  will sound, but the lock will not open.  The 
lock  will  function  for  the  Supervisor  and  Emergency  Codes  only.   See  page  7  for  the  

  battery replacement.

 

3)  Request To Enter Input

:

 

A normally open contact that when closed will unlock the lock 

for 5 seconds.  Upon activation, the lock will emit one short green flash per second. This 
feature requires hardwiring to the lock. This option will be sold as a kit which includes a 

 wiring harness that connects to the board. When the lock is in passage mode, activating  

 

4)  Peizo Sounder:

  85dBA minimum.  Short tone with each keystroke. Can be disabled by 

Supervisor code.   

  

5)  LED  Indicator

: All  three  LED’s  can  be  disabled  by  the  Supervisor  Code;  however  they 

are still active in the programming mode. Ye llow-programming mode, Green- successful 
entry, Red-Indicates input error.  

 

6)  Re-lock Duration:

 The duration that the lock remains unlocked can be adjusted from 1 to 

255 seconds.  Default at 4 seconds.   

 

7)  Hardwire:

 The  board comes  standard  with 

a  2 pin  input

 connector  to allow  hardwiring 

an  external  9  VDC  power  supply  (Part  #  784).  This  option  is  sold  as  a  kit  including  a 
wiring harness that connects to connectors provided on the board.

 

 
 

the request to enter will disable passage mode and relock the lock. 

These Program Modes 
and User Codes can be 
programmed  with the 
Supervisor Code (SC) or
the Master Code (MC)

(Hold)

(Hold)

(Hold)

(Hold)

(Hold)

(Hold)

(Hold)

Summary of Contents for E8850FL MortiseSeries

Page 1: ...ational Modes Secure Normal locked state Any assigned user code can gain access Lock relocks automatically Lockout Lockset will not accept any assigned user codes except for the Supervisor and Emergen...

Page 2: ...ous master code stays valid 3 During programming mode the yellow LED will flash continuously at normal rate To enter the lock into programming mode the key is held depressed for 3 seconds The yellow L...

Page 3: ...user to delete the emergency passage lock out codes Note if Code 61 is utilized for this purpose the functions will be completely non operational no code assigned at this point closet door User 4 Loc...

Page 4: ...default to 3131 Hold pound depressed until Yellow LED blinks continuously Enter current Master Code 1234 Yellow LED Blinks Enter Program Command Code PCC 51 Yellow LED Blinks Enter User Number 1 Yello...

Page 5: ...GRAM GUIDE User Programming Commands General Format MC PCC User LOC VAL 1 VAL 2 To Enter a Master Code MC 51 1 4 7 Digits 4 7 Digits To Enter a Emergency Code MC 51 2 4 7 Digits 4 7 Digits To Enter a...

Page 6: ...Mode 4 short beeps followed by 4 long tones will sound but the lock will not open The lock will function for the Supervisor and Emergency Codes only See page 7 for the battery replacement 3 Request T...

Page 7: ...cess The codes will not be lost during battery replacement or low power conditions Codes are stored in non volatile memory To replace the batteries remove the screw on the Battery Escutcheon and remov...

Page 8: ...0 10 12 8 eBOSS User Log Door Description Installation Date User User Name PIN Number Notes 1 Master Code 2 Emergency Code 3 Supervisor 4 Lockout 5 Passage 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21...

Page 9: ...An ASSA ABLOY Group brand 80 9150 8005 010 10 12 9 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77...

Page 10: ...materials are protected under U S copyright laws All contents current at time of publication Yale Security Inc reserves the right to change availability of any item in this catalog its design construc...

Reviews: