background image

 

 

 

Be sure to follow the below. 

 

Do not use for the medical machine and 

traffic system

 

Do  not  use  it  for  the  use  such  as  a  medical  machine  concerned 
with the life, traffic system with the possibility to give it a serious 
influence from the public society and others.

 

 
 

 

Be sure to do the matter that it is written in this instruction manual. 

 

Use in the condition and environment that this instruction 
manual mentions 

Prohibition from reconstructing, dismounting and arranging 

 

Do not reconstruct, dismount and arrange, as burning or injuring 
you.

 

Prohibition from using in-vehicle. 

 

This item isn

t for using in-vehicle that a vibration is always 

added. It may cause a fire, and dangerous due to the vibration 

 
 

 

A guarantee is only in the Japanese country. 

 

Our company isn't responsible to the duty which occurred by the 
use abroad.

 

 

 
 

 

 

 

 

 

 

Summary of Contents for ALS Series

Page 1: ...TG 000243HE0 YAMABISHI Corporation ...

Page 2: ... The three Signal Words below describe what will happen in the unlikely event of mistake being made during handling or operation If this device is improperly used people may be severely injured or killed If this device is improperly used people may suffer light to medium injures or material damage may occur Extra notes or precautions are added to operating procedures and explanations The contents ...

Page 3: ...in this instruction manual Use in the condition and environment that this instruction manual mentions Prohibition from reconstructing dismounting and arranging Do not reconstruct dismount and arrange as burning or injuring you Prohibition from using in vehicle This item isn t for using in vehicle that a vibration is always added It may cause a fire and dangerous due to the vibration A guarantee is...

Page 4: ...h temperature place Don t use it except for a plug to conform Please keep unobstructed air in the exhaust holes of UPS Power socket should be close to the UPS Don t put any liquid or object in the inside of the UPS We suggest regular maintenance to make it use this device for long time Battery exists the danger of high voltage and current Don t try to open or damage battery casing It might hurt hu...

Page 5: ...UCTION 5 The name of each department of the device 6 7 INSTALLATION 8 WIRING 9 SETTING 9 14 1 START UP and SHUT DOWN 9 2 Special Setting 2 1 Setting of Output Voltage 10 2 2 Setting of Green Mode 11 3 FUNCTIONS 12 TROUBLE SHOOTING 13 14 SPECIFICATION 15 4 ...

Page 6: ...ly and automatically under power normal condition During power failure it can provide immediate back up power from the batteries without any interruption When overload or UPS malfunction the system will automatically transfer to bypass mode and continue supplying output equipment with utility power when overload situation releases it will transfer back to inverter mode automatically while malfunct...

Page 7: ...el 6 Front Panel ON OFF Key TEST Key UPS Fault Over Currnt Green Mode Operating Bypass Operating Inverter Operating Input Battery Battery Status 100 75 25 Load Status 100 75 25 Output Cover Front View Inlet Duct ...

Page 8: ... Back View 7 Interface Slot Fan Battery Breaker Maintenance Bypass Switch Input Output Terminal Input Breaker RS232C Interface Dip Switch ...

Page 9: ...ture 10 25 is recommended to keep a battery life long Near the machine like display and so on which a magnetic influence is often taken The place to have salt and corrosion gas The place to have a vibration shock The place where powdered dust is abundant About the installation place Keep the following strictly for the safety Secure the space of more than the front 10cm and more than the rear 20cm ...

Page 10: ...r operation It usually drives is done Shut down Push the ON OFF key of the front panel and change to the bypass operation Turn off battery breaker and an input breaker in the rear An alarm rings and a device stops in about ten seconds Maintenance Bypass Switch the Maintenance Bypass Switch on manual AC power source is output There is a momentary interruption 9 Input ExternalBattery Output Terminal...

Page 11: ...ing energy mode can be set at dip switch in the rear 2 1 The setting of output voltage It can be set up by special setting as the following table ALS 5KH 200V 220V 230V 240V Restart after you finish setting of output voltage How to restart is to see the term of Start up Shut down in nine page It is the completion of the setup with this A setup is reflected by the restart of the device 10 At the se...

Page 12: ...green mode is the saving energy mode that bypass operation is done at the time of the low load Green Mode starts automatically under 360W It is not necessary to restart Be careful enough of the setup because a backup by the battery isn t completed when AC line is failed during green mode operation 11 ...

Page 13: ...rter operating If there are a few amounts of battery an alarm rings and it is returned to the inverter operating soon Turn to Bypass Push an ON OFF Key at the inverter operating it is returned to bypass operating Push an ON OFF Key at the bypass operating it is returned to inverter operating after fifteen seconds It isn t returned to the inverter operating at the over electric current time and so ...

Page 14: ...UPS still in POWER OFF status Press power on off key Buzzer sound once and the UPS Become normal UPS is proceeding controlling process Wait for a while to operate the UPS Keys on front panel don t work Key damaged Call for service Press FUNCTION key in AC mode but the UPS goes back to AC mode within less than 10 seconds Internal battery deteriorated Call service to replace batteries UPS abnormal C...

Page 15: ...eps continuously then the UPS shuts down UPS PCB abnormal Call for service Two short beep continuously Bypass Operating Push the ON OFF Key and change to inverter operating Long beep Due to over current Bypass Operating Reduce load then it turns to inverter operating automatically Two short beep No AC input DC mode Check AC power Short beep continuously A few seconds later DC mode will finish Shut...

Page 16: ... Auto Tracking Frequency Accuracy Within 0 3 Transfer Time ZERO for Line Fails or Reverse 4mSec Transfer to Bypass or Reverse Green Mode Within 360W Power factor 0 7 Backup Time 8min RechargeTime 90 8hours Output Battery Sealed Lead Acid battery Phase Single Phase 2 Wire Voltage V 173 270 Frequency 50 60Hz Input Power factor 98TYP Interface RS 232C Standard Option Option Card Alarm Signal Card etc...

Page 17: ...http www yamabishi co jp TOKYO OFFICE Email sales yamabishico jp 2 4 18 Omorikita Ota ku Tokyo Japan TEL 813 3767 8861 FAX 813 3767 7080 ...