50
4. Operating procedures
Option (RS485 communication function)
Store command
Name
Identifier
Command
Setting
Storage of settings
STR
W
N/A
(
Command necessary to store temperature and time
settings
)
Other parameters
Name
Identifier
Command
Setting
Key lock
LOC
R/W
00000
:
Key lock release
00001
:
Key lock
Operation activate/stop
RUN
R/W
00000
:
Stop
*
5
00001
:
Activate
Operation mode select
RST
R/W
00000
:
Fixed Temp operation
*5
00002
:
Program operation
Step
№
monitor
_ST
R
00000
:
Program stop
*2
00001
~
00030
:
Step 1
~
30
Operation step remaining
time monitor
_TI
R
00000
:
Time-up
*2
00001
~
99950
:
000 hour 01 min
~
999 hour 50 min
Output monitor
OM1
R
00000
:
1
st
digit
=
Heater output
2
nd
digit
=
Door input status output
3
rd
digit
=
Main output
4
th
digit
=
Time-up output or alarm output
5
th
digit
=
Overheat prevention 2 output
※
Output status
0=output OFF
1=output ON
Error monitor 1
ER1
R
00000
:
1
st
digit
=
Memory error
2
nd
digit
=
Sensor error
3
rd
digit
=
AT error
4
th
digit
=
Heater disconnection errror
5
th
digit
=
SSR short-circuit error
※
Error status
0=No error
1=Error
Error monitor 2
ER2
R
00000
:
1
st
digit
=
Door open
2
nd
digit
=
Overheat prevention 1 error
3
rd
digit
=
Overheat prevention 2 error
4
th
digit
=
Internal com/temp input circuit error
5
th
digit
=
Not used
※
Error status
0=No error
(
door closed
)
1=Error
(
door open
)
Measured temp monitor
PV1
R
(
Ex
)
00100
=
100
℃ (
thermocouple input
)
01000
=
100.0
℃ (
platinum input
)
HHHHH
=
Measured temp over scale
(
common input
)
LLLLL
=
Measured temp under scale
(
common input
)
※
The resolution of measured temp of the platinum input
is as 10 times higher as that of thermocouple input.
Summary of Contents for DKG610