Bit
Name
Function
10
SW_GATE_RESET
resets the software gate
11 ...
15
-
reserved
DS - Record set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex (3100h + EtherCAT-Slot) for access via EtherCAT
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
DIAG_EN
1
Diagnostic interrupt*
00h
00h
3100h
01h
CH0A
1
Input frequency track A
02h
01h
3101h
02h
CH1B
1
Input frequency track B
02h
01h
3102h
03h
CH2L
1
Input frequency Latch
02h
01h
3103h
04h
CH3G
1
Input frequency Gate
02h
01h
3104h
05h
CH4R
1
Input frequency Reset
02h
01h
3105h
06h
CH5
1
0 (fix)
00h
01h
3106h
07h
INT_I
1
Interrupt behavior*
80h
80h
3107h
08h
FCT_I
1
Counter function*
40h
80h
3108h
09h
MODE2_I
1
Counter mode 2*
00h
80h
3109h
0Ah
MODE3_I
1
Counter mode 3*
00h
80h
310Ah
0Bh
END_I
4
End value
00h
81h
310Bh...
310Eh
0Ch
LOAD_I
4
Load value
00h
81h
310Fh...
3112h
0Dh
HYST_I
1
Hysteresis
00h
81h
3113h
0Eh
PULSE_I
1
Pulse
00h
81h
3114h
0Fh
*) This parameter may only be transferred at STOP state.
The counter is controlled via the internal gate (I gate). The I gate is
the sum of hardware (HW) and Software gate (SW), where the
HW
gate evaluation may be deactivated via the parameterization.
HW gate:
Open (activate):
edge 0-1 at the gate input of the module
Close (de-activate):
edge 1-0 at the gate input of the module
Parameters
Control counter
VIPA System SLIO FM 050
Deployment
Fast introduction
HB300 | FM | 050-1BA00 | GB | 15-11
41