5.2.2 G5 Series
∗
1: To run/stop through the PROFIBUS-DP communications, set "3" to b1-02. To set frequency, set "3" to b1-01.
∗
2: Selecting "Continuous operation" continues the operation with the inverter single-unit at fault occurrence. Therefore,
provide some other measures (emergency stop switch, etc.) to assure safe operation.
∗
3: Enabled when "3: flux vector control" is selected at A1-02 (control mode selection). In this case, d5-01 (torque control
selection) setting alternates torque reference and torque limit.
d5-01 = 0 (speed control mode)
: Torque limit value
d5-01 = 1 (torque control mode)
: Torque reference value
∗
4: When "1: Enabled" is selected for F9-05 (factory setting), the motor may not rotate unless torque reference/torque limit is set
from the PROFIBUS-DP.
Name
Constant
No.
Operator Display
Description
Factory
Setting
Reference selection
∗
1
b1-01
Reference Source
0: Digital Operator
1: Control circuit terminals (analog inputs)
2: MEMOBUS communications (using SI-K2)
3: Option Card
4: MEMOBUS communications (for CP-717)
1
Operation method selection
∗
1
b1-02
Run Source
0: Digital Operator
1: Control circuit terminals (sequence inputs)
2: MEMOBUS communications (usingSI-K2)
3: Option Card
4: MEMOBUS communications (for CP-717)
1
External Fault Input Level from
Optical option
F9-01
E-15 Selection
0:NO contact (external fault at "1")
1:NC contact (external fault at "0")
0
External Fault from Optical Option
F9-02
EF0 Detection
0: Always detect
1: Detect during operation
0
Action for external fault from Optical
option
F9-03
EF0 ERROR SELECT
0: Deceleration to stop
1: Coast to stop
2: Emergency stop
3: Continue operation
∗
2
1
Torque reference/torque limit selection
from communications cards other than
SI-K2
∗
3
F9-05
Torq/Ref/Lmt Sel
0: Torque reference/torque limit from communications
disabled
1: Torque reference/torque limit from communications
enabled
∗
4
1
Operation selection when transmission
error detected for communications
cards other than SI-K2
F9-06
BUS Fault Sel
0: Deceleration to stop (in deceleration time C1-02)
1: Coast to stop
2: Emergency stop
(decelerate to stop in emergency stop time C1-09)
3: Continue operation
∗
2
1